3. Selection of protective device and cable specification
Type FAI-150-0151
FAI-150-0012
FAI-150-0013
Leakage
circuit
breaker
Rated current
A
20 30 32
Rated residual
Operating
current mA
30 30 30
Fuse
A
20
30
32
Power cable (mm
2
)
3×2.5
3×4
3×4
Signal line (mm
2
)
3×0.5
3×0.5
3×0.5
Note: The data above is suitable for power lines shorter than 10 meters. For
those longer than 10 meters, the wire diameters must be increased. The
maximum length of signal line is 50 meters.
4. Installation instructions and requirements
Dehumidifier must be installed by professional technicians and please do not
install it by yourselves, otherwise it may cause harm to people or damage the
machine.
A.
Installation of machine
1)
Dehumidifier should be installed in a place with good ventilation.
2)
The bolt (M 12) must be used to fix the machine body during the
installation. The machine can be fixed on the concrete foundation or
support, with the concrete foundation being firm and the support being
of great strength and anti-rust treatment.
3)
Please notice that there will be condensate water coming out from
classis during the operation. Connect the drain port to the drainage
hole in classis and link the drainpipe to enable the smooth flowing-out
of condensate water.