RTCC LED lighting controllers - User Manual
Set/Clear the Webpage Password
EY
EY asc1, asc2, asc3, asc4, asc5, asc6
This command sets the password required to access the
webpages. If
EY
is entered on its own then the password is cleared.
There are six optional parameters, which are decimal ASCII values
for a password from one to six letters. A value of 65 is ‘A’, 66 is ‘B’,
and so on, to 90 is ‘Z’.
You can set an unlock code. This can be used as a low-security way
of allowing trusted users to unlock the keypad. Ethernet commands
and the web pages still work. The setting of this command is
restored after a power cycle.
12.3.2 Lighting channel commands
Set the rating of a light
This command sets the current or voltage rating for a light. If a
current rating is being set, then the voltage rating value should be 0.
VLo,v,c
Where:
o
= output channel (1 to 4, depending on model)
v
= voltage rating (0 or 12 to 36)
c
= current rating (0 or 10mA to 3A)
Set continuous mode
The output is set to continuous mode at a percentage of full
brightness.
RSc,s
Where:
c
= output channel (1 to 4)
s
= setting in percent (s = 0 to 100)
Set switched mode
The output is set to switched mode at a percentage of full
brightness.
RWc,s
Where:
c
= output channel (1 to 4)
s
= setting in percent (s = 0 to 100)
—
51
—