Electrical connections - GAT NET.Controller M 7000

Ethernet connection (to host)

Network connections

- Ethernet to host via RJ 45 jacks.
- RS 485 bus connection to slave controllers via RJ 45 jacks.
- 200 m max. cable length per RS 485 line.

 
   

The GAT NET.Controller S 7000 must be connected to the 

 

“RS 485 SLAVES“ socket!

Recommended cabling

Ethernet: min. CAT 5 (STP)
RS 485: min. CAT 5 (STP), 200 m max. cable length per RS 485 line.

LED signaling

- RS 485 IN (yellow):  Connection to the slave controller
- RS 485 IN (green):  RS 485 communication active
- LED 1 (blue): 

For future use

- LED 2 (green/red):  Status information (see manual)

Reset and mode buttons

- RESET: 

1. Reset of controller (see manual)

 

2. Delete configuration = reset to default (see manual)

- MODE: 

Reserved for future use

Power supply

Power is connected to the MOLEX 
socket labeled “Power“. Use the supplied 
power supply unit (see technical data).

Note:  For a tidy installation, the power supply can be stored in the 

designated slot in the bottom of the controller housing.

GAT NET.Controller M 7000

Ethernet to host

Note: The GAT.NET Controller M 7000 F/ISO Light does not have any relays or optocouplers 

RS 485

SLAVES

RESET

MOD

E

LED

 1

LED

 2

RS 485

ADD-ON

Power

To the first GAT NET.Controller S 7000

Power supply GAT NET.Power Supply
(or power plug - see description below)

GAT NET.Controller M 7000

Power and slave controller connections

RS 485

SLAVES

yellow

green

RESET

MOD

E

LED

 1

LED

 2

RS 485

ADD-ON

Power

RS 485

IN

RESET

MOD

E

LED

 1

LED

 2

RS 485

OUT

Power

  Safety instructions

-  This device must be installed by qualified personnel only.
-  The applicable safety and accident prevention regulations 

must be observed.

-  Safety devices must not be removed.
-  Please observe the technical data of the device specified 

on the data sheet.

-  The device must be disconnected from the power supply 

prior to installation, assembly or dismantling.

 

The WEEE symbol on GANTNER products and their packaging 
indicates that the corresponding material must not be disposed 
of with normal household waste. Instead such marked waste 
equipment must be disposed of by handing it over to a designated 
electronic waste recycling facility. Separating and recycling this 
waste equipment at the time of disposal will help to conserve 
natural resources and ensure that it is recycled in a manner that 
protects human health and the environment. Please contact your 
local authority for further details of your nearest electronic waste 
recycling facility.

5

www.gantner.com

Valid from September 15

th

 2015 • Technical data subject to modification without notice! 

DB_GAT-NETCONTROLLER7000--EN_23.indd • Part No.: 573835

Reviews: