Reporting
Receivers Compatible with the Control Panel
SLC class A supervision trouble
ET
Exp. ID
ETNNXX0000
1
331
Exp. ID
000
SLC class A supervision trouble restore
ER
Exp. ID
ERNNXX0000
3
331
Exp. ID
000
SLC programming ended, system active
TE
0
TENN000000
3
607
00
000
SLC programming started, system shut down
TS
0
TSNN000000
1
607
00
000
SLC short circuit trouble
ET
Exp. ID
ETNNXX0000
1
332
Exp. ID
000
SLC short circuit trouble restore
ER
Exp. ID
ERNNXX0000
3
332
Exp. ID
000
Time changed event
JT
0
JTNN000000
1
625
00
000
Unable to report to account trouble
RT
Receiver #
RTNN00RRRR
1
354
00
Receiver #
Unable to report to account
trouble restore
YK
Receiver #
YKNN00RRRR
3
354
00
Receiver #
User Access Code changed
JV
0
JVNN000000
1
602
00
000
User initiated manual dialer test
RX
0
RXNN000000
1
601
00
000
Walk Test begin
TS
0
TSNN000000
1
607
00
000
Walk Test end
TE
0
TENN000000
3
607
00
000
Zone Events
Zone events are reported only when “Report by Zone” is selected
Auxiliary power trouble
FT
0000
FTNN000000
1
320
00
000
Auxiliary power trouble restore
FJ
0000
FJNN000000
3
320
00
000
CO Detector Alarm
GA
Zone #
GANN000ZZZ
1
162
00
Zone #
CO Detector Alarm Restore
GH
Zone #
GHNN000ZZZ
3
162
00
Zone #
CO Detector Supervisory Alarm
GS
Zone #
GSNN000ZZZ
1
200
00
Zone #
CO Detector Supervisory Alarm Restore
GR
Zone #
GRNN000ZZZ
3
200
00
Zone #
CO Detector Trouble
GT
Zone #
GTNN000ZZZ
1
373
00
Zone #
CO Detector Trouble Restore
GJ
Zone #
GJNN000ZZZ
3
373
00
Zone #
Detector Alarm
FA
Zone #
FANN000ZZZ
1
110
00
Zone #
Detector Alarm Restore
FH
Zone #
FHNN000ZZZ
3
110
00
Zone #
Detector trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Detector trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
External Reset/Silence/Fire Drill switch
Trouble
UT
0000
UTNN000000
1
373
00
000
External Reset/Silence/Fire Drill switch
trouble restore
UJ
0000
UJNN000000
3
373
00
000
Manual pull switch alarm
FA
Zone #
FANN000ZZZ
1
115
00
Zone #
Manual pull switch alarm restore
FH
Zone #
FHNN000ZZZ
3
115
00
Zone #
Manual pull switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Manual pull switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
Notification output trouble
FT
Group # + 1000
FTNN001GGG
1
320
00
Group #
Notification output trouble restore
FJ
Group # + 1000
FJNN001GGG
3
320
00
Group #
Positive Alarm Sequence acknowledge
switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Positive Alarm Sequence acknowledge
switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
SLC LED Module trouble
ET
0000
ETNN000000
1
333
00
000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group #