Change Trbl
The Change Trouble option should be in the “Troubles are Annunciated” Mode. This
feature is used in Special Applications where a backup system is required. Special
modules and wiring are required to utilize this option. Please consult your factory
representative for applications requiring redundant system operation.
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>4
Press Enter Key To Exit
Press Any Other Key To Toggle
I/O Troubles Are Annunciated
I/O Troubles Are Not Annunciated
Change
Dialer
This option allows the system to delay the reporting of AC failure as required by UL
when the “Dialer Is Installed” is selected. Normal reporting of AC failure troubles is
restored when the “Dialer Is Not Installed “ option is selected.
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>5
Press Enter Key To Exit
Press Any Other Key To Toggle
Dialer Is Not Installed
Dialer Is Installed
Change
Prefix
This option allows the user to change the Prefix for alarm events that occur. The
default setting is FIRE Alarm. If the panel were monitoring Gas detectors, for
example. The Prefix could be changed to GAS and therefore display GAS Alarm
during alarm conditions.
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>6
Current Alarm Prefix is: Fire
Enter New Alarm Prefix: XXXX
Do you want to clear prefix Y/N? N
Alarm Prefix is set to! Fire
Press any key to continue
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...