Gamatronic Electronic Industries Ltd.
Power+ Technical Guide
63
Table
5-3
: Log Messages "description" field
Alarm
#
Message
Explanation
01
UPSMAJ
More than 1 UPS Module is sending an alarm or fault warning.
02
UPSMIN
Single UPS Module is sending an alarm or fault warning.
03 ------
N.A.
04 ------
N.A.
05 LOADBP
Load is now running on bypass. "Data" field holds the STSW transfer
code
–
see Table
5-4 for interpretation of the STSW transfer code.
06 VIBRA_
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid
loading the log filling up.
07 OVTEMP Excess
temperature.
08
OUTFLT
No ac output to load.
09
BAT-HI
Excessive battery voltage.
10 ------
N.A.
11
BATEND
End of battery backup. Battery is discharged to shutdown limit.
12
BATLOW
Low battery voltage.
13
STSWRN
Static Switch Warning or alarm.
14
E.P.O.
Emergency Power Off is active.
15 EQ-HST
Battery is currently charging in equalizing mode, dc voltage is temporarily
increased.
16
BATFLT
Batteries failed last test.
17
USER-1
User 1 input open.
18
USER-2
User 2 input open
19
USER-3
User 3 input open.
20
AC-BRN
Input ac supply brown-out.
21
ACIN_H
Ac input excessive.
22
ACFAIL
Ac input failure.
23
STSWCM
Static Switch does not respond.
24
SLFFLT
Last controller self-test failed.
25
BAT-CB
Battery circuit breaker open.
26 CURSHR
Current Sharing fault, load current is not equally divided between
modules.
27
UPSOUT
Fault (no current) in 1 or more output stage.
28
UPSHDN
UPS shutdown by EPO, Battery Discharge, ON/OFF pressed.
29
OVLOAD
Load current is high.
30 UPS-CM One or more UPS
’
s not responding.
31 STRTUP Startup
time-stamp.
32 ------
N.A.