CENTRIC User Guide, rel. 3.4
Register
Variable name
GET Values
Remarks
260
4x0260 Output Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
261
4x0261 Output Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
262
4x0262 Output Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
263
4x0263 Output Apparent Power Line 2 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
264
4x0264 Output Power Factor Line 2
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
265
4x0265 Output Load Line 2
%
266
4x0266 Output Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
267
4x0267 Output Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
268
4x0268 Output Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
269
4x0269 Output Apparent Power Line 3 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
270
4x0270 Output Power Factor Line 3
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
271
4x0271 Output Load Line 3
%
272
4x0272 Bypass Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
273
4x0273 Bypass Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
274
4x0274 Bypass Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
275
4x0275 Bypass Apparent Power Line 1 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
276
4x0276 Bypass Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
277
4x0277 Bypass Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
278
4x0278 Bypass Apparent Power Line 2 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
279
4x0279 Bypass Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
280
4x0280 Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
281
4x0281 Bypass Apparent Power Line 3 ×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
282
4x0282 Active Alarms Count
Active alarms, except for the ones marked "ignored" or "for log only" in the controller
configuration
Register
Variable name
GET Values
Remarks
301
4x0301 General Fault
0: Alarm off
1: Alarm on
Any active alarm exists, except for the ones marked "ignored" or "for log only" in the
controller configuration