G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
CENTRIC User Guide, rel. 3.4
43
Register
Variable name
GET Values
Remarks
61
4x0061 Ups General Fault Alarm
0: Alarm off
1: Alarm on
Register
Variable name
GET Values
Remarks
201
4x0201 System Model ID
1: Mega PowerPlus
2: PowerPlus Premium
3: Centric
4:
PowerPlusPremium15
Future models for
units with touch
controller will be
added.
202
4x0202 Model Nominal Power
KW
As defined by controller settings
203
4x0203 Maximum Amount Of Modules
As defined by controller settings or the controller license
204
4x0204 Amount Of Installed Modules
As defined by controller settings, not the actual responding modules
205
4x0205 Amount Of Battery Cabinets
As defined by controller settings
206
4x0206 Multisystem Mode (Parallel
Operation)
0: Stand alone
1: Multisystem
As defined by controller settings
207
4x0207 UPS On
0: UPS off
1: UPS on
208
4x0208 All Modules Are Switched Off
0: All modules are off
1: At least one module
is on
209
4x0209 Battery Status
0: Charging
1: Discharging
2: Low
3: Depleted
4: Fault
5: Test in progress
6: Fully charged
Actual battery status as determined by controller