INSTALLATION

 

Avoid common installation errors  

Incorrect supply pipe size installed.  

Non-compliance to Australian Standards. 

Water pressure not tested before installation  

Plastic Pipe (In many brands of plastic pipe and 
associated  fittings  the  internal  diameter  is  not 
equivalent to copper). 

Lines not flushed before installation. 

No access for service. 

Valve not commissioned properly. 

 

 

 

1.  Mount face plate 

 

The stainless steel face plate is always 
mounted flush to the wall.  

 

Mount faceplate to the wall using the back 
plate and nyloc nuts (Do not over tighten 
max.35 Nm). 
Cut the studs to suit if required. 

 

Ensure button leads are pushed through the 
centre hole in back plate before tightening the 
nyloc nuts and apply a thin bead of silicon on 
the edge of the wall cut out. 

 

 

If extension leads are required, please 
contact Galvin Engineering. 
 
Do not force the faceplate to fit onto wall or 
attempt to dissamble components, as this 
could result in damage to sensor push 
button.

 

 

 
 
 
 

 
 
 
2.

 

Connect solenoid 

 

50mm flush pipe and adapter must be supplied 
by installer. 

 

Connect solenoid assemblies into the outlet 
panpipe at a minimum height of 450mm above 
the top rim of the pan.

 

 

Ensure that the solenoid is installed in the 
correct direction (the arrow on the solenoid body 
must align with the direction of water flow).

 

 

Line strainers are supplied attached to the solenoid 
valves. Removal of these strainers may void the 
warranty.  
 

Ensure no thread tape, copper swarf, sand or 
other debris enters and fouls the solenoid 
valve. 

 

Make sure solenoid valve is orientated such that 
the electrical wiring is not twisted and connectors 
are easily accessible.

 

Summary of Contents for Safe-Cell TZ-FLOWTPANMDT

Page 1: ...utton inputs and up to 2 solenoids single solenoid only for flushing units Controller is pre programmed and ready to use The solenoids will open for a specific time once the appropriate button is pres...

Page 2: ...quired to minimise ligature points and areas for concealment of contraband In addition to ensuring the products are fitted securely and in accordance with the following instructions consideration shal...

Page 3: ...mend 300mm from the centre of the outlet and at a suitable height or to project specification Cut out details for face plate Faceplate to suit wall thickness between 30mm to 240mm Ensure the cut out d...

Page 4: ...nyloc nuts and apply a thin bead of silicon on the edge of the wall cut out If extension leads are required please contact Galvin Engineering Do not force the faceplate to fit onto wall or attempt to...

Page 5: ...ic nylon or electrical parts and seals and will void the warranty Note Controller must be mounted away from any moisture or potential water splashing 4 Mount control module Attach the control module t...

Page 6: ...red please contact Galvin Specialised Do not cut the leads If the leads are too long it is recommended that any excess is coiled up and clipped to the wall 6 Connect power supply and check for correct...

Page 7: ...scanning the first thing to come up in available devices will be a Mac address that looks like this example AB EC 69 57 34 02 This will eventually change to the name of the device which is from factor...

Page 8: ...ory parameters will be downloaded to the app The Get log button will pop up the log data screen The Presets button will list all saved presets Drop Down menus First menu from left is to select the typ...

Page 9: ...p down menu The PB2 controller can be used for showers basins and pans Depend of the feature selection setting slides will appear e g there is only Run time to be set for basin Run and Lockout times f...

Page 10: ...nd Hygiene flush for full flush channel 2 and press Upload 10 Settings for shower PB2 controller is capable of controlling two buttons and two showers solenoids Select channel to be changed Select des...

Page 11: ...ck electrical connections Replace solenoid valve Water or structural damage to electrical components Replace damaged electrical components Incorrect connections Check all connections Damage to sensor...

Page 12: ...the only warranty given by the Galvin Engineering Pty Ltd With respect to the product Galvin Engineering Pty Ltd makes no other warranties express or implied Galvin Engineering Pty Ltd hereby specific...

Reviews: