11.2
REMOVAL AND INSPECTION OF CARTRIDGE
1. After checking that supply conditions are within the
specified parameters (Table 2.
), if the mixer malfunctions or should the
test results fail to fall within the specified limits
consider replacing the cartridge with a new one
(see section 11.3 Important Notes On Debris).
Afterwards, Follow the steps in section 10.2.2
Thermostatic Cartridge to remove and inspect
cartridge.
2. Set the temperature as per step 5 in section 11.1
3. Re-commission the mixer as per commissioning procedure
(See section 8.0 Commissioning). Record the mixed water temperature.
11.3
IMPORTANT NOTES ON DEBRIS
Although this product is protected by built-in filters, debris can still find its way to the thermostat housing area.
This can happen during servicing for example. Remove cartridge (See section 11.2 Removal And Inspection Of
Cartridge) and carry out an inspection.
11.4
MAINTENANCE CLEANING
On a regular basis the anti-splash nozzle should be inspected and cleaned if necessary. This should be done
immediately before sterilising is carried out.
In areas where lime scale build-up is prevalent this will have to be removed. An inhibited proprietary scale
solvent can be use
d su h kett e des ng s vent, ut t s mp rt nt t f w the m nuf turer’s gu de nes
After descaling it is important to rinse the parts thoroughly in clean water. Clean carefully and do not use
abrasive materials or scrapers.