THE MPE SERIES
1.1
FIELD OF APPLICATION
MPE air-condensed water chillers and heat pumps have been designed to cool and heat water for air conditioning and heating systems in residential or
commercial buildings. The MPE range units are intended for outdoor installation (IP24 protection degree), in a position not accessible to the public. If
protection grids are not provided (accessory) and if the machine can be reached by non-specialised personnel, access to the finned coil must be prohibited
using appropriate barriers. Do not install the unit in environments with gas or flammable dusts.
1.2
MODELS AND VERSIONS
The MPE
series includes 27 models with different in cooling only and heat pump version: All models are charged with R410A refrigerant.
The choice of some options can prevent the choice of some options or oblige the selection of other fields. To contact the Galletti for verification
Complete Unit Code M
P
E
0
0
9
C
0
0
0
0
0
0
0
0
0
0
0
0
0
1
Version
0
Single compressor
0
Tandem
T
Model (size)
0
9
Operation
C
Chiller
C
Heat pump
H
Power Supply
0
Standard 400 - 3N - 50
0
Single phase
M
400 - 3N - 50 + thermalmagnetic
2
Single Phase + thermalmagnetic
4
Expansion Valve
0
Standard valve
0
Electronic expansion valve
A
Pump and accessories
0
Not present
0
Pump - vessel - water charge valve
1
Double pump - vessel - water charge valve
2
Buffer tank
0
Not present
0
Present
S
Heat Recover (cooling only models)
0
Not present
0
Present with contact for pump
D
Condensing control
0
Not present
0
With modulating air flow
C
Antifreeze kit
0
Not present
0
Present, standard unit
E
Present, unit with pump and vessel
P
Present, unit with pump, vessel and tank
S
Acoustic insulation
0
Not present
0
Sound proofing insulation for compressor housing
1
Refrigerant circuit accessoires
0
Not present
0
Refrigerant gauge
M
Remote control
0
Not present
0
RS485 port ( carel protocol)
2
Simplified
S
Base microprocessor remote control (modbus excluded )
M
ADVANCED microprocessor remote control
X
Special coil
0
Standard
O
Copper / copper heat exchanger
R
Cataphoresis
C
“Blygold”
B
Protection grille
0
Not present
0
Present
G
Compressor options
0
Not present
0
Power factor correction capacitors
1
Soft starter
2
Power factor correction capa soft starter
3
Low temperature air water pressure switch carter heater (chiller), coil cable (PDC)
4
Control panel
1
Basic microprocessor
1
Advanced microprocessor (not available for models 04 ~ 08)
2