LCP
RG66006889-Rev.01
16
5.3
WATER CONNECTION TO THE EVAPORATOR
It is of fundamental importance that the incoming water supply is hooked up to the
connection marked “Water Inlet”.
Otherwise the evaporator would be exposed to the risk of freezing since the antifreeze thermostat would
not be able to perform its function; moreover the reverse cycle would not be activated in the cooling
mode, resulting in additional risks of malfunctioning.
The dimensions and position of plumbing connections are shown in the dimension tables at the end of
the manual.
The water circuit must be set up in such a way as to guarantee that the nominal flow rate
of the water supplied to the evaporator remains constant (+/- 15%) in all operating
conditions.
The compressors often work intermittently, since the chilling requirements of the user generally do not
coincide with the output of LCP unit. In systems containing little water, where the thermal inertia of the
water is lower, it is a good idea to check that the water content in the section delivering to users satisfies
the condition below:
Ns
Sh
Cc
V
V
= water content in user section
[m3]
Sh
= specific heat of the fluid
[J/(kg/°C)]
=
fluid
density
[kg/m3]
∆
= minimum time lapse between 2 compressor restarts [s]
∆
T
= allowed water T differential
[°C]
Cc
=
Cooling
capacity
[W]
Ns
= N° of capacity control steps
This check must be performed even though it must considered that the LCP units cannot
be configured with the tank on board.
Inertial Tank
Ts °C
Incoming water
T
Outgoing water
T