5
FM
All copying, even partial, of this manual is strictly forbidden
FC66003740 - Rev 01
4
RATED TECHNICAL DATA
1 Water temperature 7-12°C, air temperature D.B. 27°C, W.B. 19°C (47% relative humidity)
2 Water temperature 50°C, water flow rate same as in cooling mode, air inlet temperature 20°C
3Sound power measured according to standards ISO3741 and ISO3744
4Sound pressure level measured at a distance of 1 m with a directivity factor of 4
RATED TECHNICAL DATA OF FM FAN COIL UNITS
Model
22 / 23
32 / 33
42 / 43
Supply voltage
V - ph - Hz
230-1-50 / 220-1-60
Speeds
1
2
3
1
2
3
1
2
3
Total cooling capacity (1)
kW
1,37
1,64
2,07
1,94
2,40
3,02
2,68
3,28
3,74
Sensible cooling capacity (1)
kW
0,99
1,20
1,52
1,40
1,47
2,22
1,95
2,40
2,74
Water flow rate (1)
l/h
234
281
356
335
414
518
457
565
641
Pressure drop (1)
kPa
11
15
22
18
26
38
25
36
45
FCEER - nominal value
168
187
183
FCEER - Class
B
A
B
Heating capacity (2)
kW
1,75
2,12
2,70
2,48
2,61
3,93
3,45
4,20
4,87
Pressure drop (2)
kPa
9
12
18
15
22
32
20
29
36
FCCOP - nominal value
216
230
238
FCCOP - Class
B
Air flow rate
m3/h
290
370
500
370
445
645
570
740
876
Power input
W
8
10
13
10
13
20
13
20
30
Sound power level (3)
dB/A
35
40
48
38
43
53
45
52
57
Sound pressure level (4)
dB/A
27
32
40
30
35
45
37
44
49
Water content
dm3
0,43
0,86
Water connections (female gas)
inches
1/2
Condensate drainage connection
inches (mm)
5/8 (16)
Dimensions H x L x P
mm
876/228/300
Net weight
kg
12,00
13,00
14,00