12 MODBUS

INPUT REGISTERS

Description

Address 

Type 

Remark

Dip switch 1 status

400000

R

Dip switch 2 status

400001

R

Room temperature sensor

400002

R

Ti1 temperature sensor

400003

R

Ti2 temperature sensor

400004

R

Error code

400005

R

Bit0= Room temperature sensor error
Bit1= Ti1 temperature sensor error
Bit2= Ti2 temperature sensor error
Bit3= Float switch error
Bit4= Indoor coil low temperature protection
Bit5= Indoor coil over heat protection
Bit6= Reserved
Bit7= Electrical heater failure
Bit8= Motor1 error
Bit9= Motor2 error
Bit10= System parameters error
Bit11= Reserved
Bit12= Reserved
Bit13= Reserved
Bit14= Reserved
Bit15= Reserved

Fan speed status

400006

R

Low=04(H)
Medium= 02(H)
High= 01(H)

Mode status

400007

R

Cooling mode= 01(H)
Dehumidify mode= 02(H)
Fan mode= 04(H)
Heating= 08(H)

Setting temperature status

400008

R

Testing only

Room temperature in wall pad status

400009

R

Room temperature in main PCB status

400010

R

Unit type

400011

R

4-pipe= 03, 2-pipe= 02
This setting is configured by dip switch

EC motor 1#RPM

400012

R

EC motor 2#RPM

400013

R

Summary of Contents for FM 22

Page 1: ...2 0 kW 3 7 kW FM GB TECHNICAL MANUAL HIGH WALL MOUNTED FAN COIL UNITS WITH BLDC MOTOR AND INCORPORATED VALVE...

Page 2: ...ORKS 11 9 WALLPAD 13 10 Installation requirements 14 11 Routine maintenance 15 12 MODBUS 16 Thetechnicalanddimensionaldataprovidedhereinmayundergochangesinconnection with product improvements Operatin...

Page 3: ...l the functions of the unit and the room temperature HEAT EXCHANGER Uprated heat exchanger made with copper piping and high efficiency alumi nium fins with hydrophilic surface treatment complete with...

Page 4: ...e the deviation measured and adapt the rpm accordingly The derivative logic analyzes the change speed thus assuring little variations Watertemperaturereadinganddefinitionofminimumworkingtemperatures A...

Page 5: ...1 94 2 40 3 02 2 68 3 28 3 74 Sensible cooling capacity 1 kW 0 99 1 20 1 52 1 40 1 47 2 22 1 95 2 40 2 74 Water flow rate 1 l h 234 281 356 335 414 518 457 565 641 Pressure drop 1 kPa 11 15 22 18 26 3...

Page 6: ...Pa FM 22 FM 23 1 1590 1080 274 14 1370 990 234 11 2 1890 1300 324 19 1640 1200 281 15 3 2370 1630 407 29 2070 1520 356 22 FM 32 FM 33 1 2270 1530 389 24 1940 1400 335 18 2 2770 1620 475 33 2400 1470 4...

Page 7: ...PH Qw Dpw W l h kPa W l h kPa FM 22 FM 23 1 1330 230 8 1380 119 3 2 1620 281 12 1690 148 4 3 2070 360 18 2170 187 6 FM 32 FM 33 1 1880 328 15 1950 169 5 2 1920 335 15 1970 173 5 3 3000 522 33 3150 27...

Page 8: ...orbidden FC66003740 Rev 01 2 Way Valve Body 3 Way 4 Outlet Differential pressure Chart Differential pressure Chart Valve Dimensions mm DN A B C D D15 G1 2 52 47 19 5 63 Valve Dimensions mm Valve Model...

Page 9: ...26 8 57 49 2 48 6 50 0 49 4 48 1 40 5 30 3 20 3 51 43 3 43 0 44 4 44 1 41 3 32 5 21 8 18 6 45 37 All copying even partial of this manual is strictly forbidden FC66003740 Rev 01 6 OVERALL DIMENSIONS 5...

Page 10: ...cable control Yellow green Auxiliary heating contact Auxiliary cooling contact 7 WIRING DIAGRAMS Make the electrical connections with the power supply disconnected in accordance with current safety re...

Page 11: ...hot valve 8 MASTER SLAVE NETWORKS The FM fan coil units are equipped with a PCB suitable for the implementation of master slave networks with up to 32 units Depending on the control panel used on the...

Page 12: ...from the master unit Theslaveunitcanbesetlocallyonadesiredsettingbymeansofthelocalcontroller providedtherearenosubsequentchangestothesettingsofthemasterunit The slave units can be set individually fo...

Page 13: ...ect the day of the week from Sunday to Saturday Or used for programming the weekly switching on and off via the timer to select the day of the week Network button for the network control Clock setting...

Page 14: ...free of obstructions The air should flow freely The wall the unit is mounted on must be sufficiently rigid so as not to resonate and produce noise The position should permit easy access for installin...

Page 15: ...cables for the sensors Install a filter if harmful interferences are present in the power supply Filter 11 ROUTINE MAINTENANCE The material must undergo maintenance in order to retain its characterist...

Page 16: ...TIONS Error code Description Definition 01 01H Invalid commands Received commands beyond valid commands 02 02H Invalid data address Data addresses beyond valid data address 03 03H Invalid data Data be...

Page 17: ...d wall pad and set timer function Hour 300007 W Calibration wired wall pad and set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wa...

Page 18: ...low temperature protection Bit5 Indoor coil over heat protection Bit6 Reserved Bit7 Electrical heater failure Bit8 Motor1 error Bit9 Motor2 error Bit10 System parameters error Bit11 Reserved Bit12 Re...

Page 19: ...19 FM All copying even partial of this manual is strictly forbidden FC66003740 Rev 01...

Page 20: ...Wolf Schweiz AG Dorfstrasse 147 CH 8802 Kilchberg Telefon 41 43 500 48 00 Fax 41 43 500 48 19 info wolf klimatechnik ch www wolf klimatechnik ch...

Reviews: