FC66005368
All copying, even partial, of this manual is strictly forbidden
19
GIVK - Insulating shell for VKS
GIVK valve insulation shell avoid forming condensate into the valve body. The water connections are provided both left and right.
V2VSTD - 2 way valve
The kit is made up of:
2-way valve/2 connections with built-in by-pass, maximum operating pressure 16 bar.
Electrothermal actuator with ON/OFF functions (total opening time 4 minutes), 230 V power supply.
Hydraulic kit for installing the valve on the heat exchanger.
Available versions with water connections on the left and on the right.
V2VSTD - 3 way valve
The kit is made up of:
3-way valve/4 connections with built-in by-pass, maximum operating pressure 16 bar.
Hydraulic kit for installing the valve on the heat exchanger, complete with 2 holders for balancing and regulating the fan coil unit.
Available versions with water connections on the left and on the right.
MYCOMFORT LARGE - wall-mounted microprocessor control having the following main features:
• Room air temperature reading and adjustment
• Room humidity reading and adjustment
• Water temperature reading (water probe as an optional)
• Manual and automatic adjustment of fan speed
• Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature,
with a neutral zone that can be selected in the range from 2° to 5°C.
• Clock and hourly timer-programmed operation
• 2 Analogue outputs for controlling modulating evices 0-10 V
• 2 Digital outputs for controlling (On/Off) external devices (novoltage contacts)
• Serial port for Bus connection
The controller is equipped with a large display (3”) to show and set all the functions of the unit.
MCSWE - water temperature sensor for microprocessor controls model EVO, MYCOMFORT
Directly connected to the microprocessor controllers EVO and MYCOMFORT to measure the water temperature through the heat exchanger.
If the temperature detected is less than 17°C, the unit will operate in the cooling mode and the controller will use the summertime temperature scale (19 - 31°C);
if the temperature detected is greater than 37°C the unit will function in the heating mode and the controller will use the wintertime temperature scale (14 /
26°C). If the temperature detected by the probe is in the range of 17°C to 37°C, the controller will inhibit operation of the fan coil unit.
MCSUE - Humidity sensor for EVO and MYCOMFORT microprocessor controller
Directly connected to the microprocessor controllers EVO and MYCOMFORT, it enables the control of the heating element ventilation (if present, as support in
heating mode) and the automatic cooling/heating changeover according to the water temperature.
BV - Water drip tray
This accessory tray is used to collect the condensate from the valve and the pressure regulator. The drip tray is reversible for both left and right version.