FC66005368
All copying, even partial, of this manual is strictly forbidden
11
4
RATED TECHNICAL DATA
ART-U
10
20
30
40
50
Speed
min med max min med max min med max min med max min med max
Control voltage
V
4,50 5,60 6,40 4,90 7,00 10,0 5,40 7,00 10,0 5,50 7,00 10,0 5,50 7,00 10,0
Rated air flow
m³/h
110
141
179
190
275
391
295
390
528
412
529
715
474
609
824
Power supply
V-ph-Hz
230 - 1 - 50
Power input
(E)
W
4
5
6
7
11
17
10
14
23
14
20
32
16
23
36
Total cooling capacity
(1)
kW
0,39 0,69 0,80 0,93 1,32 1,67 1,44 2,01 2,44 1,96 2,62 3,16 2,29 3,17 3,72
Sensible cooling capacity
(1)
kW
0,29 0,50 0,63 0,69 0,99 1,28 1,05 1,44 1,84 1,43 1,97 2,43 1,66 2,26 2,83
Total cooling capacity
(2)(E)
kW
0,39 0,69 0,80 0,93 1,31 1,66 1,43 2,00 2,42 1,95 2,60 3,13 2,28 3,14 3,69
Sensible cooling capacity
(2)(E)
kW
0,29 0,49 0,62 0,68 0,98 1,26 1,04 1,43 1,82 1,42 1,95 2,39 1,65 2,24 2,79
FCEER class
(E)
C
B
B
B
B
Water flow
(1)
l/h
67
116
134
161
227
282
247
329
395
338
441
528
395
517
622
Water pressure drop
(1)(E)
kPa
1
1
2
4
8
11
12
20
27
9
15
20
14
23
31
Heating capacity
(3)(E)
kW
0,73 0,93 1,05 1,28 1,70 2,14 1,98 2,41 2,94 2,65 3,22 3,92 3,08 3,74 4,56
FCCOP class
(E)
C
Water pressure drop
(3)(E)
kPa
1
1
2
4
8
11
12
20
27
9
15
20
14
23
31
Heating capacity
(4)(E)
kW
0,56 0,73 0,87 1,04 1,38 1,81 1,52 2,09 2,48 1,96 2,66 3,34 2,49 3,07 3,74
Water flow
(4)
l/h
98
126
146
169
238
303
261
359
413
360
457
557
416
528
644
Water pressure drop
(4)(E)
kPa
1
1
2
4
7
12
11
20
27
8
14
20
14
20
28
Total sound power level
(5)(E)
dB(A)
37
44
49
39
47
54
41
47
54
42
47
54
42
47
54
(1) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity)
(2) According to EN1397:2015
(3) Inlet water temperature 50°C, water flow rate same as in cooling mode, air temperature 20°C
(4) Water temperature 45°C / 40°C, air temperature 20°C
(5) Sound power measured according to standards ISO 3741 and ISO 3742
(E) EUROVENT certified data
5 WEIGHTS
Mod.
kg
ART-U 010
12
ART-U 020
14
ART-U 030
17
ART-U 040
19
ART-U 050
21