ACQVARIA

TECHnICAL MAnuAL

10

4 INSTALLATION

WARNING:

 unit installation and start-up must be entrusted 

to competent personnel and performed in a workmanlike 

manner, in accordance with current regulations.

WARNING:

 

It is mandatory to install the 3-way (or 2-way) 

valve accessory in order to avoid the circulation of cold 

water in the exchanger if the unit is not operated for 

long periods of time, with the fan off. Install the auxiliary 

water drip tray, provided together with the base unit, in 

order to prevent valve kits from dripping.

For each unit an (IL) switch should be mounted on the power 

supply, with opening contacts at a distance of at least 3 mm 

and a suitable protection fuse (F) .

WARNING:

 before carrying out any operation, check that 

the voltage and frequency of the unit correspond exactly 

to those of the main power supply.

WARNING:

 Install the unit, circuit breaker (IL) and/or any re-

mote controls in a place out of reach of persons who may be 

taking a bath or shower. 

WARNING:

 keep the unit's grille in its original packaging 

until final assembly.

RECOMMENDED:

 to ensure optimal comfort (homoge-

neous air temperature in the room), it is recommended not 

to exceed a heat exchanger water inlet temperature of 55 °C.

WARNING:

 during a shutdown for installation, in the event 

of a connection to a fresh air intake or an ambient tempera-

ture close to 0 °C, there is a risk of the pipes freezing. Provide 

drainage for the water circuit.

4.1 

INSTALLATION REQUIREMENTS

The fan coils should be installed in a position where the room 

can be heated or cooled evenly, on ceilings able to support their 

weight. Store the unit in its packaging until you are ready to in-

stall it.

For installation and use of accessories, please refer to the relative 

technical sheets.

Install any remote 

control panel

 in an easily accessible position 

allowing the user to set the functions while ensuring an accurate 

reading of the ambient temperature, if provided.

Avoid therefore:

 

Ū positions directly exposed to sunlight;

 

Ū positions exposed to direct currents of warm or cold air

 

Ū placing obstacles that impede an accurate temperature 

reading

NB:

 The water sensor, where present, must be mounted in 

the appropriate trap on the valve kit, on the InLET pipe.

Water sensor holder

1

 

Ū If a valve kit other than the one suggested is used, it is neces-

sary to install the sensor on the InLET pipe, by means of the 

special copper socket filled with conductive paste.

 

Ū Lastly, the sensor must be properly isolated to ensure that it 

reads the water temperature correctly.

NB:

 The air and humidity sensors, where present, must be at-

tached in the appropriate section located in the intake area 

of the base unit.

Sensor retainer

1

Make the plumbing connections to the heat exchanger and, 

where the cooling function is to be used, to the condensate 

drainage outlet.

WARNING:

In normal operation, particularly with the fan at minimum 

speed and ambient air with high relative humidity, conden-

sation may form on the air outlet and on some external parts 

of the unit.

To avoid such issues while always remaining within the oper-

ating limits envisaged for the unit, it is necessary to limit the 

inlet temperature of the water inside the heat exchanger. In 

particular, the difference between the air dew point  (T

A

,D

P

)  

and the inlet water temperature (T

W

) must nOT exceed 14 

°C, according to the following relationship:  

T

W

>T

A

,D

P

-14 

°C

Example

: in the case of ambient air at 25 ° C with 75% rela-

tive humidity, the dew point temperature is about 20 ° C and 

therefore the inlet temperature of the water in the battery 

must be greater then:

 

Ū 20-14 = 6 °C in order to avoid condensation on a fancoil 

equipped with a valve.

Fan coil with valve

Air temperature dry bulb (°C)

21

23

25

27

29

31

33

Relative 

humidity %

40

5

5

5

5

5

5

5

50

5

5

5

5

5

6

8

60

5

5

5

5

7

9

11

70

5

5

6

8

9

11

13

80

5

6

8

10

12

14

16

90

6

8

10

12

14

16

18

If the valves are not installed, there could be abundant con-

densation, especially if the unit is not operated for long pe-

riods of time.

During wintertime periods of quiescence, drain water from the 

system, to prevent ice from forming. If anti-freeze solutions are 

used, check for their freezing point using the table below.

Summary of Contents for ACQVARIA AQ10Q0B0

Page 1: ...device Recess ceiling mount PLUS Reliability and sturdiness in a compact design Fresh air with direct or mixed introduction Heat exchanger up to 3 rows Condensate drainage pump for height differences...

Page 2: ...nery Directive the Electromagnetic Compatibility Directive the Electrical Safety Directive and the Pressure Equipment Directive Fulfillment of the Ecodesign requirements is fully in keeping with the e...

Page 3: ...IGHTS p 16 7 PERFORMANCES p 17 8 SOUND LEVELS p 18 9 ELECTRICAL CONNECTION DIAGRAMS p 19 10 OVERALL DIMENSIONS p 31 11 ACCESSORIES p 35 11 1 2 OR 3 WAY MOTOR DRIVEN VALVE KITS p 38 11 2 PRESSURE INDEP...

Page 4: ...cent rooms The design and colour RAL9003 or RAL9010 of the air intake and diffusion louvre guarantee optimal integration into the sus pended ceiling panels Easy access to the air filter for cleaning o...

Page 5: ...display MCSUE Humidity sensor for MY COMFORT medium e large EVO MCSWE Water sensor for MYCOMFORT and EVO controllers Electronic microprocessor control panels TED 2T Electronic controller for AC fan co...

Page 6: ...t 2 4 FAN DRIVE ASSEMBLY Three speed electrical motor directly connected to a centrifu gal fan with backward curving blades with profile optimised for stable operation at all speeds 2 5 CONDENSATE COL...

Page 7: ...Locking clips 2 Tie rods 3 Condensate drip tray 4 Condensate drainage pump 5 Heat exchanger 6 Fan drive assembly 7 External insulation 8 Internal insulation 9 Lateral sheet metal 10 Sheet metal back 1...

Page 8: ...Condensate drip tray 4 Condensate drainage pump 5 Heat exchanger 6 Fan drive assembly 7 External insulation 8 Internal insulation 9 Lateral sheet metal 10 Sheet metal back 11 Reinforcement brackets 1...

Page 9: ...4 5 2 3 6 4 2 5 1 4 2 5 1 5 4 Height Y m 2 0 2 3 2 8 2 0 2 6 3 4 2 4 2 7 3 2 2 3 2 6 3 1 2 6 3 1 3 3 Distance Z m 2 3 2 6 3 1 2 3 2 9 3 9 3 1 3 5 4 1 2 9 3 3 3 9 3 3 3 9 4 2 Air range 4T Model AQ10 AQ...

Page 10: ...nlight positions exposed to direct currents of warm or cold air placing obstacles that impede an accurate temperature reading NB The water sensor where present must be mounted in the appropriate trap...

Page 11: ...ement a logic that makes it possible to set a fixed speed between minumum medium and maximum or automatic speed modulation The automatic logic varies the analog signal to the motor be tween minimum me...

Page 12: ...312 Pay attention to the excess length B of the suspension rod Fig 7 it may interfere with the unit s electrical box Place the fan coil unit in the suspended ceiling orienting the side with the water...

Page 13: ...WC66000496 All copying even partial of this manual is strictly forbidden 13 Fig 5 AQ 40 50 60 Fig 6 18 8 11 Fig 7 1 Nut washer 2 Washer nut lock nut Fig 8 Fig 9 AQ10 20 Fig 10 AQ40 50 60...

Page 14: ...ember to at tach it again after installation Lift the grille to remove it from the control panel Fig 11 To install the front panel Fig 12 Turn the two locking clips 5 downwards Attach the control pane...

Page 15: ...e F A 2 2 2 Fuses type gG ACQVARIA AQ50Q0B0 AQ60Q0B0 Speed min med max min med max Total cooling capacity 1 kW 5 16 6 11 8 24 6 34 8 61 9 73 Sensible cooling capacity 1 kW 3 68 4 37 6 10 4 59 6 40 7 3...

Page 16: ...rea of power cables 4 mm 1 00 1 00 1 00 1 00 Power supply cable type N07V K Safety fuse F A 2 2 2 2 Fuses type gG 1 Water temperature 7 C 12 C air temperature dry bulb 27 C wet bulb 19 C 47 relative h...

Page 17: ...etailed report which includes performances dimensional drawings tender specifications and the economic offer Product selection Filters to make the identification of the requested product easier Perfor...

Page 18: ...4 7 12 0 40 max 54 2 51 9 49 5 45 3 42 0 32 2 19 5 51 AQ60Q0B0 min 44 1 41 8 38 2 35 3 27 7 14 7 12 0 40 med 54 2 51 9 49 5 45 3 42 0 32 2 19 5 51 max 58 0 57 1 53 8 49 8 46 1 39 3 27 2 56 4 pipes ACQ...

Page 19: ...end Check that the mains electricity supply is compatible with the voltage shown on the unit rating plate 9 1 My Comfort Base wiring diagram for AQ 10 20 M Fanmotor MP Condensate drainage pump FLOAT F...

Page 20: ...on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue common motor BN FLOA...

Page 21: ...it breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH M White minimum speed mot...

Page 22: ...ast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue common motor BN F...

Page 23: ...Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH M White minimum spe...

Page 24: ...supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue comm...

Page 25: ...hot and cold F 2A fuse not supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH...

Page 26: ...upplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor B...

Page 27: ...hot and cold F 2A fuse not supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor W...

Page 28: ...supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor...

Page 29: ...fuse not supplied IL Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor W...

Page 30: ...Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed...

Page 31: ...den 31 10 OVERALL DIMENSIONS 10 1 Dimensional drawing AQ 10 20 2 pipes LEGEND 1 Electric box 2 Condensate discharge 10 3 Water outlet 1 2 female gas 4 Water inlet 1 2 female gas 1 m 1 m 1 m 1 m 614 21...

Page 32: ...sional drawing AQ 40 50 60 2 pipes LEGEND 1 Electric box 2 Condensate discharge 10 3 Water outlet 3 4 female gas 4 Water inlet 3 4 female gas 1 m 1 m 1 m 1 m 830 830 n 1 1 350 30 793 860 485 860 92 5...

Page 33: ...es LEGEND 1 Electric box 2 Condensate discharge 10 3 Cooling exchanger water outlet 1 2 gas F 4 Cooling exchanger water inlet 1 2 gas F 5 Heating exchanger water outlet 1 2 gas F 6 Heating exchanger w...

Page 34: ...ctric box 2 Condensate discharge 10 3 Cooling exchanger water outlet 3 4 gas F 4 Cooling exchanger water inlet 3 4 gas F 5 Heating exchanger water inlet 1 2 gas F 6 Heating exchanger water outlet 1 2...

Page 35: ...withintheheatexchanger or on the room temperature with a neutral zone that can be selected in the range from 2 to 5 C The controller is equipped with a large display 3 to show and set all the function...

Page 36: ...onal manual or automatic switch on the basis of air temperature Water consent on the basis of temperature LED503 Recess wall mounted microprocessor control The proposed microprocessor control panels f...

Page 37: ...OFF servo control it acts directly on the valve shutter Hydraulic plumbing kit made with copper piping and brass connectors VKM 3 way motor driven modulating valve complete with hydraulic kit It cont...

Page 38: ...in the figures from page p 38 Pressure drops of the valve hydraulic kit assembly are calculated using the following formula PW QW KV 2 Where PW pressure drop in kg cm2 QW water flow rate in m3 h KV w...

Page 39: ...forbidden 39 3 way valve kit 2 pipes AQ 10 20 1 Water outlet 2 Water inlet NOTE The actuator is not shown 1 3 2 2 way valve kit 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot water outl...

Page 40: ...kit 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot water outlet 4 Hot water inlet NOTE The actuators are not shown 1 3 2 4 5 2 way valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water i...

Page 41: ...bidden 41 3 way valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water inlet NOTE The actuator is not shown 1 3 2 2 way valve kit 4 pipes AQ 40 50 60 1 Cold water outlet 2 Cold water inlet 3 Hot water o...

Page 42: ...y ON OFF or modulating function total opening time 3 minutes Hydraulic kit with O ring for connection with the exchanger and paper gasket for connection with the valve Brackets for fastening the hydra...

Page 43: ...l of this manual is strictly forbidden 43 2 way valve kit VPIC 2 pipes AQ 10 20 1 Water outlet 2 Water inlet 1 2 2 way valve kit VPIC 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot wate...

Page 44: ...cal manual 44 2 way VPIC valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water inlet 2 1 2 way VPIC valve kit 4 pipes AQ 40 50 60 1 Cold water outlet 2 Cold water inlet 3 Hot water outlet 4 Hot water i...

Page 45: ...FOR INTAKE OF FRESH AIR TO BE TREATED The units are equipped with 3 fresh air inlets positioned in the corners This air mixes with the air drawn in from the indoor en vironment and is then treated by...

Page 46: ...nit must be ther mally insulated to prevent the formation of surface conden sation The following graphs show the air flow values as a function of the pressure drops of the duct at different fan speed...

Page 47: ...fresh air is introduced into the installation room by passing the heat exchanger by means of a supply fin of the unit The dimensions of diameter D are Model D ACQVARIA 10 20 150 ACQVARIA 40 50 60 180...

Page 48: ...proceed as follows Figure 21 1 Before performing any work on the unit disconnect it from the power supply 2 Remove the screws 1 securing the retainers 2 on each side 3 To open the grille 3 push on th...

Page 49: ...g the screws Remove the tank handling it with care Clean the inside of the tank Check that the heat exchanger is clean If needed use a vac uum cleaner with a rubber tip to remove dust being careful no...

Page 50: ...via Romagnoli 12 a 40010 Bentivoglio BO Italy Ph 39 051 8908111 Fax 039 051 8908122 UNI EN ISO 9001 and UNI EN ISO 45001 www galletti com...

Reviews: