Galleon 1K User Manual Download Page 3

 

1. Important Safety Warning 

Please comply with all warnings and operating instructions in this manual strictly. Save this 

manual properly and read carefully the following instructions before installing the unit. Do not 
operate  this  unit  before  reading  through  all  safety  information  and  operating  instructions 
carefully 

 

1-1. Transportation 

 

Please transport the UPS system only in the original package to protect against shock 
and impact. 

 

1-2. Preparation 

 

Condensation may occur if the UPS system is moved directly from cold to warm 
environment. The UPS system must be absolutely dry before being installed. Please 
allow at least two hours for the UPS system to acclimate the environment.   

 

Do not install the UPS system near water or in moist environments. 

 

Do not install the UPS system where it would be exposed to direct sunlight or near 
heater. 

 

Do not block ventilation holes in the UPS housing. 

 

1-3. Installation 

 

Do not connect appliances or devices which would overload the UPS system (e.g. 
laser printers) to the UPS output sockets.   

 

Place cables in such a way that no one can step on or trip over them.   

 

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

 

The UPS can be operated by any individuals with no previous experience. 

 

 

Connect the UPS system only to an earthed shockproof outlet which must be easily 
accessible and close to the UPS system.   

 

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your 
computer) to connect the UPS system to the building wiring outlet (shockproof 
outlet).   

 

Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS 
system.   

 

When installing the equipment, it should ensure that the sum of the leakage current 

of the UPS and the connected devices does not exceed 3.5mA. 

 

1-4. Operation 

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof socket outlet) during operations since this would cancel the protective 
earth of the UPS system and of all connected loads.   

 

The UPS system features its own, internal current source (batteries). The UPS output 
sockets or output terminals block may be electrically live even if the UPS system is not 
connected to the building wiring outlet.   

 

In order to fully disconnect the UPS system, first press the OFF/Enter button to 
disconnect the mains.   

 

Prevent no fluids or other foreign objects from inside of the UPS system.   

Summary of Contents for 1K

Page 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Page 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Page 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Page 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Page 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Page 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Page 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Page 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Page 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Page 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Page 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Page 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Page 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Page 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Page 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Page 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Page 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Page 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...