Galleon 1K User Manual Download Page 14

12 

 

 

01: Output voltage setting 

Interface 

Setting 

 

Parameter 3: Output voltage 

For 200/208/220/230/240 VAC models, you may choose the 
following output voltage: 

200:

 presents output voltage is 200Vac 

208:

 presents output voltage is 208Vac 

220:

 presents output voltage is 220Vac 

230:

 presents output voltage is 230Vac (Default) 

240:

 presents output voltage is 240Vac 

For 100/110/115/120/127 VAC models, you may choose the 
following output voltage: 

100:

 presents output voltage is 100Vac 

110:

 presents output voltage is 110Vac 

115: 

presents output voltage is 115Vac 

120: 

presents output voltage is 120Vac (Default) 

127: 

presents output voltage is 127Vac 

 

02: Frequency Converter enable/disable 

Interface 

Setting 

 

Parameter 2: 

Enable or disable converter mode. You may 

choose the following two options:

 

CF ENA: 

converter mode enable 

CF DIS: 

converter mode disable (Default) 

 

03: Output frequency setting 

Interface 

 

Setting 

 

Parameter 2: Output frequency setting.   

You may set the initial frequency on battery mode: 

BAT 50:

 presents output frequency is 50Hz 

BAT 60:

 presents output frequency is 60Hz 

If converter mode is enabled, you may choose the following 
output frequency: 

CF 50: 

presents output frequency is 50Hz 

CF 60: 

presents output frequency is 60Hz 

 

04: ECO enable/disable 

Interface 

Setting 

 

Parameter 2: 

Enable or disable ECO function. You may 

choose the following two options:   

ENA:

 ECO mode enable 

DIS: 

ECO mode disable (Default) 

 

05: AECO enable/disable 

Interface 

Setting 

 

ENA:

 Advanced ECO mode enable 

DIS:

 Advanced ECO mode disable (Default) 

Summary of Contents for 1K

Page 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Page 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Page 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Page 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Page 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Page 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Page 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Page 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Page 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Page 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Page 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Page 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Page 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Page 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Page 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Page 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Page 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Page 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...

Reviews: