Galleon 1K User Manual Download Page 18

16 

 

3-6. Operating Mode Description 

Operating mode  Description 

LCD display   

Online mode 

When the input voltage is within acceptable 

range, UPS will provide pure and stable AC power 
to output. The UPS will also charge the battery at 
online mode.   

 

ECO mode

 

Energy saving mode:   

When the input voltage is within voltage 
regulation range, UPS will bypass voltage to 
output for energy saving. The UPS will also 

charge the battery at ECO mode. 

 

AECO mode   
(Advanced 
Efficiency 
Corrective 
Optimizer) 

When the input voltage is within setting range (

±

3%Vo max), UPS will bypass voltage to output 
for energy saving. PFC and INVERTER are off at 
this mode. 

 

Frequency 
Converter mode 

When input frequency is within 40 Hz to 70 Hz, 
the UPS can be set at a constant output 

frequency, 50 Hz or 60 Hz. The UPS will still 
charge battery under this mode. 

 

Battery mode 

When the input voltage is beyond the acceptable 
range or power failure, the UPS will backup 

power from battery and alarm is sounding every 
5 seconds.   

 

Bypass mode 

When input voltage is within acceptable range 
but UPS is overload, UPS will enter bypass mode 

or bypass mode can be set by front panel. Alarm 
is sounding every 10 seconds.   

 

Standby mode 

UPS is powered off and no output supply power, 
but still can charge batteries. 

 

Fault mode 

When a fault has occurred, the ERROR icon and 
the fault code will be displayed. 

 

 
3-7. Faults Reference Code 

Fault event 

Fault code    Icon 

Fault event 

Fault code   

Icon 

Bus start fail 

01 

Inverter output short 

14 

 

Bus over 

02 

Battery voltage too high 

27 

 

Bus under 

03 

Battery voltage too low 

28 

 

Inverter soft start fail 

11 

Over temperature 

41 

x

 

Inverter voltage high 

12 

Over load 

43 

 

Inverter voltage Low 

13 

Charger failure 

45 

x

 

 

Summary of Contents for 1K

Page 1: ...Rackmount Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 1 User Manual...

Page 2: ...el view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 6 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD displ...

Page 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...d and long run models Please refer to the following model table Model No Type Model No Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1K NEMA 1 5K...

Page 6: ...to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 2 3 Setup the U...

Page 7: ...line cable Step 5 Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 6 Turn on the UPS Press th...

Page 8: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Page 9: ...below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove a...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage...

Page 12: ...by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mod...

Page 13: ...gh loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable...

Page 14: ...verter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Outp...

Page 15: ...age Default 6V 07 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable De...

Page 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 10 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Page 17: ...2 3 4 setting the maximum charger current in 2 3 4 Ampere When the UPS is long run model the available setting options are 1 2 4 6 8 1 2 4 6 8 setting the maximum charger current in 1 2 4 6 8 Ampere...

Page 18: ...ncy 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS will backup power from battery and alar...

Page 19: ...ding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range So...

Page 20: ...flashing on LCD display and alarm is sounding every 2 seconds The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon...

Page 21: ...d Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as...

Page 22: ...acity Charging Current 1 5 A Max Charging Voltage 27 4 VDC 1 41 1 VDC 1 41 1 VDC 1 54 8VDC 1 82 1VDC 1 82 1VDC 1 Long run Model Type Depending on application Battery Numbers 2 3 3 4 6 6 Charging Curre...

Reviews: