3E4720 Gallagher T12 Reader | Edi  on 12 | May 2023
Copyright © Gallagher Group Limited

 Cable 

distance

Cable type

Cable format*

HBUS 

single reader 

connected 
using data 

only in a single 

cable

Cardax IV 

single reader 

connected 
using data 

only in a single 

cable***

HBUS/Cardax IV

single reader 

connected using  

power and 

data in a single 

cable****

CAT 5e or 
be  er**

4 twisted pair each 2 x 
0.2 mm

(24 AWG)

500 m (1640   )

200 m (650   )

100 m (330   )

BELDEN 
9842**
(shielded)

2 twisted pair each 2 x 
0.2 mm

(24 AWG)

500 m (1640   )

200 m (650   )

100 m (330   )

SEC472

4 x 0.2 mm

2  

Not 

twisted pairs (24 AWG)

400 m (1310   )

200 m (650   )

100 m (330   )

SEC4142

4 x 0.4 mm

2  

Not 

twisted pairs (21 AWG)

400 m (1310   )

200 m (650   )

150 m (500   )

C303900/
C303901 
Gallagher 
HBUS Cable

2 Twisted pair each 2 
x 0.4 mm

(21 AWG, 

Data) and 2 x 0.75 mm

Not Twisted Pair (~18 
AWG, Power)

500 m (1640   )

200 m (650   )

450 m (1490   )

* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for op  mal HBUS RS485 performance.
*** Not applicable for Bluetooth® enabled reader installa  ons.
**** Tested with 13.6V at start of cable.

Notes:

• 

Shielded cable may reduce the obtainable cable length.  Shielded cable should be 
grounded at the Controller end only.  

• 

If other cable types are used, opera  ng distances and performance may be reduced 
depending on the cable quality.

• 

HBUS allows up to 20 readers to be connected to a single cable.  Each reader requires at 
least 9 Vdc to func  on correctly.  The cable length and the number of readers connected 
will have an impact on the voltage at each reader.

Distance between readers

The distance separa  ng any two proximity readers must not be less than 200 mm (8 in) in all direc  ons.  
When moun  ng a proximity reader on an internal wall, check that any reader 

fi

 xed to the other side of 

the wall is not less than 200 mm (8 in) away.

200 mm

 

   200 mm

Summary of Contents for T12

Page 1: ...d Gallagher T12 Reader Installa on Note T12 MIFARE Reader Black C300420 T12 MIFARE Reader White C300421 T12 Mul Tech Reader Black C300440 T12 Mul Tech Reader White C300441 High Sec T12 Reader Black C3...

Page 2: ...ss and it should not be relied on as such To the extent permi ed by law all express or implied or other representa ons or warran es in rela on to the informa on are expressly excluded Neither Gallaghe...

Page 3: ...oduct Codes Card Technologies Supported NFC Access for Android Supported From Bluetooth Access Supported From HBUS Comms Supported From Cardax IV Comms Supported From T12 MIFARE Reader C300420 C300421...

Page 4: ...2 3 Cabling The Gallagher T12 Reader requires a minimum cable size of 4 core 24 AWG 0 2 mm2 stranded security cable This cable allows the transmission of data 2 wires and power 2 wires When using a s...

Page 5: ...vices HBUS Device Terminate HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device Terminate Remove the on board termina on jumper RS485 1 T or Star circuits are not permi ed between...

Page 6: ...0 m 1640 200 m 650 450 m 1490 The matching of wire sizes to equivalent wire gauges are only approximate Recommended cable types for op mal HBUS RS485 performance Not applicable for Bluetooth enabled r...

Page 7: ...the 13 mm 1 2 inch diameter centre hole this is the centre hole for which the building cable will exit the moun ng surface and the four fixing holes 2 Run the building cabling out through the centre h...

Page 8: ...rdax IV Reader connec on Posi ve Red Nega ve Black HBUS Termina on Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue Cardax IV Reader 5 Fit the facia assembly into the bezel by clipping th...

Page 9: ...cess mode is Secure Flashes Green Access has been granted Flashes Red Access has been denied Flashes Blue Reading a Gallagher mobile creden al LED squiggle Cardax IV indica on 3 Flash Amber No communi...

Page 10: ...sing the default configura on for a reader in Command Centre Changing the configura on may vary the current value 5 The unpo ed variant C300440 01 does not have any environmental protec on 6 The unpo...

Page 11: ...perienced radio TV technician for help This device complies with Industry Canada licence exempt RSS standard s Opera on is subject to the following two condi ons 1 this device may not cause interferen...

Page 12: ...Gallagher Group Limited IMPORTANT This picture is not to scale therefore use the measurements provided 35 mm 1 38 26 mm 1 29 mm 1 14 86 mm 3 39 13 mm 1 2 diameter hole for cable 86 mm 3 39 25 mm 1 30...

Reviews: