3E4720 Gallagher T12 Reader | Edi  on 12 | May 2023
Copyright © Gallagher Group Limited

Before you begin

2.1 Shipment 

contents

Check the shipment contains the following items:

• 

1 x Gallagher T12 Reader facia assembly

• 

1 x Gallagher T12 Reader bezel

• 

1 x M3 Torx Post Security screw

• 

2 x M3.5 Phillips drive 

fi

 xing screws

• 

4 x 25 mm No.6 self tapping, pan head, Phillips drive 

fi

 xing screws

• 

4 x 40 mm No.6 self tapping, pan head, Phillips drive 

fi

 xing screws

2.2 Power 

supply

The Gallagher T12 Reader is designed to operate at a supply voltage of 13.6Vdc measured at the 
reader terminals.  The opera  ng current draw is dependant on the supply voltage at the reader.  
For a MIFARE reader, at 13.6 Vdc the current draw is 50 mA (idle).  During creden  al read, beeper 
and LED ac  vity, the current will momentarily reach 77 mA (maximum).  For a Mul   Tech reader, 
at 13.6 Vdc the current draw is 80 mA (idle) and will momentarily reach 142 mA (maximum).  The 
power source should be linear or a good quality switched-mode power supply.  The performance 
of the reader may be a

 ected by a low quality, noisy power supply.

2.3 Cabling

The Gallagher T12 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm

2

) stranded 

security cable.  This cable allows the transmission of data (2 wires) and power (2 wires).  When 
using a single cable to carry both power supply and data, both the power supply voltage drop 
and data requirements must be considered. For good engineering design it is recommended that 
the voltage at the reader should be approximately 12 Vdc.

 

HBUS cabling topology

The HBUS communica  ons protocol is based on the RS485 standard and allows the reader to 
communicate over a distance of up to 500 m (1640   ).  

The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or 
"Star" topology should not be used between devices).  Should "Star" or "Home-Run" wiring be 
required, the HBUS 4H/8H Modules and the HBUS Door Module allow mul  ple HBUS devices to 
be individually wired to the one physical loca  on.

The end devices on the HBUS cable should be terminated using 120 ohms resistance.  To 
terminate the Gallagher Controller 6000, connect the supplied on-board termina  on jumpers 
to the Controller.  To terminate a reader, connect the orange (termina  on) wire to the green 
(HBUS A) wire.  Termina  on is already included at the HBUS Module, (i.e. each HBUS port is 
permanently terminated at the module).

Summary of Contents for T12

Page 1: ...d Gallagher T12 Reader Installa on Note T12 MIFARE Reader Black C300420 T12 MIFARE Reader White C300421 T12 Mul Tech Reader Black C300440 T12 Mul Tech Reader White C300441 High Sec T12 Reader Black C3...

Page 2: ...ss and it should not be relied on as such To the extent permi ed by law all express or implied or other representa ons or warran es in rela on to the informa on are expressly excluded Neither Gallaghe...

Page 3: ...oduct Codes Card Technologies Supported NFC Access for Android Supported From Bluetooth Access Supported From HBUS Comms Supported From Cardax IV Comms Supported From T12 MIFARE Reader C300420 C300421...

Page 4: ...2 3 Cabling The Gallagher T12 Reader requires a minimum cable size of 4 core 24 AWG 0 2 mm2 stranded security cable This cable allows the transmission of data 2 wires and power 2 wires When using a s...

Page 5: ...vices HBUS Device Terminate HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device HBUS Device Terminate Remove the on board termina on jumper RS485 1 T or Star circuits are not permi ed between...

Page 6: ...0 m 1640 200 m 650 450 m 1490 The matching of wire sizes to equivalent wire gauges are only approximate Recommended cable types for op mal HBUS RS485 performance Not applicable for Bluetooth enabled r...

Page 7: ...the 13 mm 1 2 inch diameter centre hole this is the centre hole for which the building cable will exit the moun ng surface and the four fixing holes 2 Run the building cabling out through the centre h...

Page 8: ...rdax IV Reader connec on Posi ve Red Nega ve Black HBUS Termina on Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue Cardax IV Reader 5 Fit the facia assembly into the bezel by clipping th...

Page 9: ...cess mode is Secure Flashes Green Access has been granted Flashes Red Access has been denied Flashes Blue Reading a Gallagher mobile creden al LED squiggle Cardax IV indica on 3 Flash Amber No communi...

Page 10: ...sing the default configura on for a reader in Command Centre Changing the configura on may vary the current value 5 The unpo ed variant C300440 01 does not have any environmental protec on 6 The unpo...

Page 11: ...perienced radio TV technician for help This device complies with Industry Canada licence exempt RSS standard s Opera on is subject to the following two condi ons 1 this device may not cause interferen...

Page 12: ...Gallagher Group Limited IMPORTANT This picture is not to scale therefore use the measurements provided 35 mm 1 38 26 mm 1 29 mm 1 14 86 mm 3 39 13 mm 1 2 diameter hole for cable 86 mm 3 39 25 mm 1 30...

Reviews: