Gallagher C300420 Installation Note Download Page 6

Page 6   

3E4290 Gallagher T12 Reader | Edition 1 | August 2016

 

Copyright © Gallagher Group Limited

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

Terminate

Remove the on-board 

termination jumper

RS485 1

"T" or "Star" circuits are 

not permitted between 

HBUS devices

HBUS

 

Device

Terminate

HBUS

 

Device

Controller 6000

HBUS

 

Device

"T" or "Star" circuits are 

not permitted between 

HBUS devices

Controller 6000

H1

H4
H8

H5

HBUS

 

Device

Terminate

HBUS

 

Device

Terminate

HBUS Module

HBUS

 

Device

HBUS

 

Device

Terminate

HBUS

 

Device

Terminate

HBUS

 

Device

 

Cable distance

Cable type

Cable format*

HBUS  

single reader 

connected using 

data only in a 

single cable

Cardax IV 

single reader 

connected using 

data only in a 

single cable***

HBUS/Cardax IV 

single reader 

connected using  

power and data 

in a single cable

CAT 5e or 

better**

4 twisted pair

 

Each 2 x 0.2 mm

(24 AWG)

500 m (1640 ft)

200 m (650 ft)

100 m (330 ft)

BELDEN 9842**

 

(shielded)

2 twisted pair

 

Each 2 x 0.2 mm

(24 AWG)

500 m (1640 ft)

200 m (650 ft)

100 m (330 ft)

SEC472

4 x 0.2 mm

Not twisted 

pairs (24 AWG)

400 m (1310 ft)

200 m (650 ft)

100 m (330 ft)

SEC4142

4 x 0.4 mm

Not twisted 

pairs (21 AWG)

400 m (1310 ft)

200 m (650 ft)

150 m (500 ft)

* The matching of wire sizes to equivalent wire gauges are only approximate.

Summary of Contents for C300420

Page 1: ...r Edition 1 August 2016 Copyright Gallagher Group Limited Gallagher T12 Reader Installation Note T12 Mifare Reader Black C300420 T12 Mifare Reader White C300421 T12 Multi Tech Reader Black C300440 T12...

Page 2: ...ess and it should not be relied on as such To the extent permitted by law all express or implied or other representations or warranties in relation to the information are expressly excluded Neither Ga...

Page 3: ...016 Copyright Gallagher Group Limited Contents 1 Introduction 4 2 Before you begin 4 3 Distance between readers 7 4 Installation 7 5 LED indications 10 6 Accessories 10 7 Technical specifications 11 8...

Page 4: ...th the Gallagher Controller IMPORTANT HBUS compatibility HBUS communications are supported with sites running Gallagher Command Centre vEL7 00 software or later IMPORTANT Multi Tech readers Using dual...

Page 5: ...ments must be considered Although the reader is specified to operate at 9 Vdc for good engineering design it is recommended that the voltage at the reader should be approximately 12 Vdc HBUS cabling t...

Page 6: ...e HBUS Device Cable distance Cable type Cable format HBUS single reader connected using data only in a single cable Cardax IV single reader connected using data only in a single cable HBUS Cardax IV s...

Page 7: ...This equipment contains components that can be damaged by electrostatic discharge Ensure both you and the equipment are earthed before beginning any servicing The Gallagher T12 Reader is designed to...

Page 8: ...le Connect the wires for the appropriate reader you wish to interface either an HBUS Reader or a Cardax IV Reader as shown in the following diagrams Note Mobile credential readers must be connected as...

Page 9: ...g a T10 Torx Post Security screwdriver through the hole at the bottom of the bezel to secure the facia assembly Note The Torx Post Security screw needs only to be lightly tightened Bezel Fit screw to...

Page 10: ...been granted Flashes Red Access has been denied Flashes Blue Reading a Gallagher mobile credential LED squiggle Cardax IV indication 3 Flash Amber No communications with the Controller On Green or Re...

Page 11: ...70 C Note Direct sunlight may increase the internal reader temperature above the ambient temperature level Humidity 0 95 non condensing3 Environmental protection IP68 Impact rating IK07 Unit dimensio...

Page 12: ...frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Page 13: ...t Gallagher Group Limited 9 Mounting dimensions IMPORTANT This picture is not to scale therefore use the measurements provided 35 mm 1 38 26 mm 1 29 mm 1 14 86 mm 3 39 13 mm 1 2 diameter hole for cabl...

Reviews: