Page  5   

3E4290 Gallagher T12 Reader | Edition 1 | August 2016

 

Copyright © Gallagher Group Limited

2.2  Power supply

The Gallagher T12 Reader is designed to operate over a supply voltage range of 9 - 16 Vdc 

measured at the reader terminals.  The operating current draw is dependant on the supply 

voltage at the reader.  For the Mifare reader, at 13.6 Vdc the current draw is 84 mA (idle).  During 

card read, beeper and LED activity, the current will momentarily reach 113 mA (maximum).  For 

the Multi Tech reader, at 13.6 Vdc the current draw is 100 mA (idle) and will momentarily reach 

124 mA (maximum).  The power source should be linear or a good quality switched-mode power 

supply.  The performance of the reader may be affected by a low quality, noisy power supply.

2.3  Cabling

The Gallagher T12 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm

2

) stranded 

security cable.  This cable allows the transmission of data (2 wires) and power (2 wires).  When 

using a single cable to carry both power supply and data, both the power supply voltage drop 

and data requirements must be considered.  Although the reader is specified to operate at 9 

Vdc, for good engineering design it is recommended that the voltage at the reader should be 

approximately 12 Vdc.

 

HBUS cabling topology

The HBUS communications protocol is based on the RS485 standard and allows the reader to 

communicate over a distance of up to 500 m (1640 ft).  

The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or 

"Star" topology should not be used between devices).  Should "Star" or "Home-Run" wiring be 

required, the HBUS 4H/8H Modules and the HBUS Door Module allow multiple HBUS devices to 

be individually wired to the one physical location.

The end devices on the HBUS cable should be terminated using 120 ohms resistance.  To 

terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers 

to the Controller.  To terminate a reader, connect the orange (termination) wire to the green 

(HBUS A) wire.  Termination is already included at the HBUS Module, (i.e. each HBUS port is 

permanently terminated at the module).

Connect the on-board 

termination jumper

Controller 6000

RS485 1

HBUS

 

Device

"T" or "Star" circuits are 

not permitted between 

HBUS devices

HBUS

 

Device

Terminate

HBUS

 

Device

HBUS

 

Device

HBUS

 

Device

Summary of Contents for C300420

Page 1: ...r Edition 1 August 2016 Copyright Gallagher Group Limited Gallagher T12 Reader Installation Note T12 Mifare Reader Black C300420 T12 Mifare Reader White C300421 T12 Multi Tech Reader Black C300440 T12...

Page 2: ...ess and it should not be relied on as such To the extent permitted by law all express or implied or other representations or warranties in relation to the information are expressly excluded Neither Ga...

Page 3: ...016 Copyright Gallagher Group Limited Contents 1 Introduction 4 2 Before you begin 4 3 Distance between readers 7 4 Installation 7 5 LED indications 10 6 Accessories 10 7 Technical specifications 11 8...

Page 4: ...th the Gallagher Controller IMPORTANT HBUS compatibility HBUS communications are supported with sites running Gallagher Command Centre vEL7 00 software or later IMPORTANT Multi Tech readers Using dual...

Page 5: ...ments must be considered Although the reader is specified to operate at 9 Vdc for good engineering design it is recommended that the voltage at the reader should be approximately 12 Vdc HBUS cabling t...

Page 6: ...e HBUS Device Cable distance Cable type Cable format HBUS single reader connected using data only in a single cable Cardax IV single reader connected using data only in a single cable HBUS Cardax IV s...

Page 7: ...This equipment contains components that can be damaged by electrostatic discharge Ensure both you and the equipment are earthed before beginning any servicing The Gallagher T12 Reader is designed to...

Page 8: ...le Connect the wires for the appropriate reader you wish to interface either an HBUS Reader or a Cardax IV Reader as shown in the following diagrams Note Mobile credential readers must be connected as...

Page 9: ...g a T10 Torx Post Security screwdriver through the hole at the bottom of the bezel to secure the facia assembly Note The Torx Post Security screw needs only to be lightly tightened Bezel Fit screw to...

Page 10: ...been granted Flashes Red Access has been denied Flashes Blue Reading a Gallagher mobile credential LED squiggle Cardax IV indication 3 Flash Amber No communications with the Controller On Green or Re...

Page 11: ...70 C Note Direct sunlight may increase the internal reader temperature above the ambient temperature level Humidity 0 95 non condensing3 Environmental protection IP68 Impact rating IK07 Unit dimensio...

Page 12: ...frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Page 13: ...t Gallagher Group Limited 9 Mounting dimensions IMPORTANT This picture is not to scale therefore use the measurements provided 35 mm 1 38 26 mm 1 29 mm 1 14 86 mm 3 39 13 mm 1 2 diameter hole for cabl...

Reviews: