background image

 

 

validate that the correct Security Code has been entered.  
Once the correct Security Code has been entered, the Bar 
Graph will begin to flash the 4-digit software version 
number. If not, you must repeat this step (2).

   

 

 
3.

 

In  SETUP mode,  the parameters listed under each 
numeric button can be accessed by pressing the MENU 
button and then pressing a Number button  (See page 5). 

 
4.

 

Pressing the MENU button repeatedly will cycle through 
the menus.  Do this until the appropriate LED 
illuminates for the menu you want to access.  You can 
verify which MENU you are in by looking at the LED 
Bar Graph on the left side of the front panel.  Currently, 
there are six MENUS  to choose from.  These menus 
correspond to LED 0, LED 1, LED 2, LED 3, LED 4 and 
LED 5 respectively.    

 
 
5.

 

Next, press the numeric button on the keypad for the 
parameter you want to access.  For example: pressing the 
MENU button twice and then pressing the 5-button will 
access the Overspeed parameter. 

 
6.

 

Remember that a flashing RUN/SETUP LED indicates 
that you are in SETUP mode.  To exit SETUP mode and 
save changes to parameters, press and hold the 
RUN/SETUP button until the RUN/SETUP LED stops 
flashing and stays ON. 

 
 
GAC recommends that the user take time to fully understand 
the following items before attempting to start the engine or 
going any further: 
 
1.

 

Understanding the Keypad, Menus and Parameters 
(Pages 4, 5 & 6). 

 
2.

 

Understanding the LED Display Modes (Page 5 & 6). 

 
 
3.

 

Entering SETUP mode & Security Code. 

 
4.

 

Configuring the necessary basic parameters and saving 
changes. 

 

Summary of Contents for IGC700 Series

Page 1: ...low through GAC s SmartView software With this greater flexibility conditions like Low Air Pressure Low Oil Level Low Coolant Level and Door Open can be configured and monitored with the proper sensor...

Page 2: ...2 Diagram 1...

Page 3: ...re for more information Fuel Solenoid Connect the Fuel Solenoid to Terminal F The second wire of the Fuel Solenoid is connected the negative of the Battery Variable Speed Potentiometer Although a 2k 1...

Page 4: ...access the various parameters available you must first be in SETUP mode Once in SETUP mode choose which MENU you need access to and then press the number button on the keypad that corresponds to the...

Page 5: ...o choose from These menus correspond to LED 0 LED 1 LED 2 LED 3 LED 4 and LED 5 respectively 5 Next press the numeric button on the keypad for the parameter you want to access For example pressing the...

Page 6: ...age from 0 to 100 Pressing the arrow buttons increases or decreases the value You may have to press the button several times to illuminate the next LED This is due to the difference in resolution betw...

Page 7: ...ED 0 Droop Overspeed Start Fuel Begin Point Menu 1 LED 1 Input P Trip Point Input R Trip Point Menu 2 LED 2 ON Input P Delay Input R Delay Menu 3 LED 3 Input Q Trip Point Input S Trip Point Menu 4 LED...

Page 8: ...s R S according to one of the four settings shown in Table 1 on page 3 If you have selected Variable Speed mode then skip over Fixed Speed Operation and go directly to Variable Speed Operation below F...

Page 9: ...RPM value for this parameter 3 Enter the desired RPM value as a four digit number For example 275 RPM would be entered as 0 2 7 5 and press ENTER After pressing the Enter button the Bar Graph will fla...

Page 10: ...de indicated by the RUN SETUP LED being steady ON OPERATING AND TUNING Verify Settings Before starting the engine with the IGC700 connected please follow the steps listed below 1 Apply power but do no...

Page 11: ...o adjust the Derivative parameter Range Setting This function will double or triple the Gain and Stability parameter ranges by reducing the resolution This is useful when large amounts of gain and sta...

Page 12: ...n 70mA max continuous plus actuator current Actuator Current Range 25o C 77 F Inductive Load Max 10 Amps continuous Speed Sensor Signal 0 5 120 Volts RMS Discrete Outputs Alarm AUX Sink up to 500mA 25...

Page 13: ...LED should turn off If it doesn t that means the Overspeed limit was exceeded during starting Recheck Flywheel Teeth Overspeed and Speed settings Cycling the power on the IGC will remove the Overspeed...

Page 14: ...t starting may be due to an extremely long fuel ramp This can be disabled by Entering Setup mode and accessing the Starting Fuel Function Menu 0 Button 6 Next enter 0 0 0 0 and press ENTER This enters...

Page 15: ...MINIMUM RPM SPEED MENU 1 Button 7 When doing this you should also verify the Bar Graph displays a higher reading for MAX RPM SPD than for MIN RPM SPD Make sure the FLYWHEEL TEETH parameter is correct...

Page 16: ...ameter L8 Gain Stability Derivative These LED s will come on individually when their respective parameters are being accessed for adjustment The Derivative LED also lights during the Cranking Cycle L9...

Page 17: ...Not Used Not Used Not Used 5 Flywheel Teeth Overspeed Input P Trip Point Input P Delay Input Q Trip Point Input Q Delay 6 Start Fuel Ramp Start Fuel Begin Point Input R Trip Point Input R Delay Input...

Page 18: ...18 December 2003 PTI1061 Rev XA Preliminary...

Reviews: