Installation & operation
Placement
Install the UPS in a protected area that is free of
excessive dust and has adequate air flow. Please
place the UPS far from other units at least 20 cm to
avoid interference. DO NOT operate the UPS when
temperature and/or humidity are outside the specific
limits (please check technical specifications).
Charging
Plug in the AC input cord to the wall outlet. For the best results it is
suggested to charge battery at least 6 hours before first use. The UPS
charges its battery while connecting to the utility.
Equipment connection
Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the power switch of UPS
unit, then the connected devices will be protected by UPS unit.
Network connection (phone/modem)
In order to protect a network connection, please connect a network cable from the wall jack outlet to the IN jack
of the UPS. Then connect a network cable from the OUT jack of the UPS to the network device.
Communication port connection
It is possible to connect the UPS to a personal computer through the USB communication port, using the
supplied cable.
ViewPower is an UPS management software that allows users to control and monitor UPS straightly from PC
monitor. Insert ViewPower software CD or download ViewPower software from website address
http://www.power-software-download.com, then follow on-screen instructions to complete software installation.
Once the computer has restarted, ViewPower will boot up as a plug-in and will appear as an orange icon in the
taskbar, in the lower right corner.
Switching On/Off
To turn on the UPS, press the ON/OFF button for 2 seconds (LED indicator will light up). To turn off the UPS,
please press again the ON/OFF button for 2 seconds (LED indicator will light off).
Cold Start function
In case of extended power failure it’s possible to start the
UPS directly by batteries, supplying connected devices
for some minutes.
Trouble-shooting
Use the table below to solve minor problems. If any abnormal situations occur that are not listed above, please
call service technician for assistance.
Problem
Possible cause
Solutions
No LED on
Low battery
Charge the UPS at least 6 hours
Battery fault
Replace the battery with one of the same type
The UPS is not turned on
Press the power switch again (for 2 seconds)
to turn on the UPS
Alarm continuously
sounds when the
mains is normal
The UPS is overloaded
Remove some loads first. Before reconnecting
equipment, please verify that the load matches the
UPS capability specified in technical specifications
When power fails,
back-up time is
shortened
The UPS is overloaded
Turn off the UPS and remove some critical load
Low battery
Charge the UPS at least 6 hours
Defective battery
Replace the battery with one of the same type
UPS works always on
battery mode
Power cord is loose or disconnected
Reconnect the power cord properly
Technical specifications
Model
650
850
1000
1500
2000
Capacity
650VA/
360W
850VA/
480W
1000VA/
600W
1500VA/
900W
2000VA/
1200W
INPUT
Voltage
220/230/240 VAC
Voltage range
162-290 VAC
OUTPUT
Voltage
+/-10%
Voltage range
Typical 2-6 ms, 10ms max.
Wave form **
Simulated Sine Wave **
BATTERY
Type and number
12V/7Ah x1
12V/9Ah x1
12V/7Ah x2
12V/9 Ah x2
Charging time
4-6 hours recover to 90% capacity
SIZE AND WEIGHT
Dimension DxWxH, (mm)
300 x 101 x 142
320 x 130 x 182
Net weight (kg)
4.4
5.0
8.2
10.4
11
ENVIRONMENT
Humidity
0-90 % RH @ 0-40°C (no condensing)
Noise level
Less than 40 dB
Monitoring software
Supports Windows, Linux, Unix, MAC
Mark/Compliance
CE/LVD 2014/35/EU EN62040-1 / EMC 2014/30/EU EN62040-2 Prestazioni EN62040-3 (VI)
* For improvement purpose product specifications could change without further notice
** NOTE: The Pseudosinusoidal, StepWave or Simulated waveform is not suitable for powering PCs or Servers with Active PFC
Technology. For these systems, refer to the Pure Sine Wave UPS models