![G-Tec LibraPro User Manual Download Page 55](http://html1.mh-extra.com/html/g-tec/librapro/librapro_user-manual_3086406055.webp)
0MNLIBRAPROK10NPENUA 01 Pag. 55 / 57
Electrical Data
10
15
20
30
40
60
80
INVERTER
Rated power Pf 0.9 inductive [kVA] 10
15
20
30
40
60
80
Active power Pf 1 [kW] 9
13,5
18
27
36
54
72
Rated voltage
400Vca 3-phase+N (configurable from 380V to 415V)
Rated voltage adjustment field
from 360 to 420V
Rated frequency [Hz]
50 or 60 (configurable)
Static variation
± 1%
Dynamic variation
± 5%
Recovery time within ± 1%
20ms
Conforms to standard EN 62040-3, class 1
Current peak factor (Ipeak/Irms as per EN 62040-3)
3:1
Voltage distortion with linear load
1% (typical), 2% (max)
Voltage distortion with non linear load
(EN 62040-3)
< 3%
Stability of frequency with Inverter synchronized with
the by-pass mains
± 2% (adjustable from ± 1% to ± 6% from control
panel)
Stability of frequency with Inverter not synchronized
with the by-pass mains
± 0.05%
Speed of frequency variation
1Hz/sec
Dissymmetry of the phase voltages with balanced and
unbalanced load
≤ 1%
Voltage phase shift with balanced and unbalanced load
120 ± 1°el
Overload with reference to the rated power: three phase
110% for 60’, 125% for 10’ , 150% for 1’
Short circuit current phase / phase
180% for 1 second with current limiting
phase / neutral
300% for 1 second with current limiting
Electrical Data
10
15
20
30
40
60
80
BY-PASS
Rated voltage
400Vca 3-phase + N (configurable from 380V to 415V)
Rated voltage tolerance
± 15% (adjustable from ± 10% to ± 25% from panel)
Rated frequency [Hz]
50 or 60 (auto-sensing)
Frequency tolerance
± 2% ( ± 1% ÷ ± 6% from control panel)
Switching onto by-pass with synchronized Inverter
(UPS in “Normal Mode”)
No break
Switching onto by-pass with Inverter out of sync
(UPS in “Normal Mode”)
~ 100 ms
Switching from by-pass to Inverter (UPS in “Stand-by
On mode”)
from 2 to 5ms
Delay in transfer onto Inverter after switching onto by-
pass
4 s
Power overload capacity of the by-pass line (kVA]
110 % for 60 minutes, 125 % for 10 minutes, 150 % for
1 minute
i²t SCR bypass (25°C, 8÷10ms) [A²s]
11k
20k
Short circuit capacity of the by-pass line (x rated
current): 1 s
7
4,6
3,5
5
7
7
7,5
500ms
7
4,6
3,5
6
8
8
8
200ms
8
5
4
6
8
8
9
100ms
8
5
4
7
9
9
9
10ms
12
8
6
8
12
12
14
Summary of Contents for LibraPro
Page 2: ...Pag 2 57 0MNLIBRAPROK10NPENUA 01...
Page 6: ...Pag 6 57 0MNLIBRAPROK10NPENUA 01 This page is left blank intentionally...
Page 25: ...0MNLIBRAPROK10NPENUA 01 Pag 25 57 This page is left blank intentionally...
Page 35: ...0MNLIBRAPROK10NPENUA 01 Pag 35 57 This page is left blank intentionally...
Page 51: ...0MNLIBRAPROK10NPENUA 01 Pag 51 57 This page is left blank intentionally...
Page 53: ...0MNLIBRAPROK10NPENUA 01 Pag 53 57 This page is left blank intentionally...