Pag. 16 / 57 0MNLIBRAPROK10NPENUA 01
3.2
Mains, load and battery connections
The operations described in this chapter must be carried out exclusively by a
specialized technician
.
The first connection to be made is the earth conductor.
THE LIBRAPROMUST NOT OPERATE WITHOUT AN EARTH CONNECTION
Before making the connection, open all the switches on the device and ensure that the UPS is completely isolated
from the power sources: battery and AC power line. More specifically, check that:
- the UPS input line or lines are completely isolated;
- the battery cabinet disconnector / fuse (if present) is open;
- all the UPS disconnectors - SWIN, SWBY, SWOUT and SWMB - are in the open position;
- check with a multimeter that there are no dangerous voltages on the terminal board.
For connection of the power cables to the terminal boards, refer to the “INSTALLATION DRAWINGS”
provided with the UPS and with the battery cabinet, if present.
Input neutral
The power supply to the LIBRAPRO input (by-pass line) must be three-phase with neutral.
The neutral conductor is necessary only on by-pass line
.
Input line without neutral.
The transformer must be inserted either on the mains supply line or on the by-pass line (as shown in the drawings).
-transformer on the bypass line only
-The transformer supply bypass and mains lines
MAINS LINE
UPS
LOAD
3Ph+N
or
OPTIONAL
MAINS LINE
UPS
LOAD
3Ph+N
BY-PASS LINE
or
OPTIONAL
Summary of Contents for LibraPro
Page 2: ...Pag 2 57 0MNLIBRAPROK10NPENUA 01...
Page 6: ...Pag 6 57 0MNLIBRAPROK10NPENUA 01 This page is left blank intentionally...
Page 25: ...0MNLIBRAPROK10NPENUA 01 Pag 25 57 This page is left blank intentionally...
Page 35: ...0MNLIBRAPROK10NPENUA 01 Pag 35 57 This page is left blank intentionally...
Page 51: ...0MNLIBRAPROK10NPENUA 01 Pag 51 57 This page is left blank intentionally...
Page 53: ...0MNLIBRAPROK10NPENUA 01 Pag 53 57 This page is left blank intentionally...