GOV Basic(Governor Basic Setting)
GOV Basic(Governor Basic Setting)
(6) Stick sw.: Stick switch
The governor can be activated by throttle stick position.
[Setting method]
Touch the "Stick SW" button to enter the setting mode.
"Sure?" Is displayed. Operate the throttle stick to the position where you
want to turn Governor ON. If you touch the [Yes] button, the ON position is
memorized. This stick switch function is always enabled when the next "ON
/ OFF sw" is "INH" or the "Governor ON / OFF switch is not set by S.BUS set-
ting.
When governor is turned on and off by transmitter throttle stick
The data is set so that the governor can be
turned on and off with the transmitter throttle
stick position. The following describes this op-
eration.
• Throttle stick over set point and more than 60%
of set rotation speed.
ON
*This is the setting value of "Gov. On. Revo: Gov-
ernor ON revolution setting".
• Throttle stick held at the set point or more Re-
mains.
ON
• Throttle stick position is below the set point se-
lected.
OFF
When idle up
• When the throttle curve is set at idle up, and when the throttle output is over the set
value (initial value: 30%), the governor will always and remain ON even if the stick is
lowered to the bottom.
(OFF at slow side)
Set point or less
0%
100%
(Governor operating point)
Set speed
The stick is at, or be-
yond the set point and
is 60% of the rotation
speed value of the gov-
ernor.
When you activate the switch, the direction setting of the switch is displayed.
Select the switch ON / OFF direction (Normal / Reverse).
When turning on / off governor with switch
Select the ON / OFF switch channel with "GOV sw channel" on "SBUS BASIC"
menu.
Setting the switch to the ON position turns on, or enables the
governor. The following describes this operation.
• Switch set to on position and engine running at 60% or more
of set speed
ON
• Throttle stick set to maximum slow position
ON
• Switch set to off position
OFF
(7) ON/OFF sw.: Governor on/off switch
This parameter allows the user to turn the governor on or off via a switch
on the transmitter. Choose INH if you do not want to use it.
Governor can be turned
on and off by a switch.
When Battery Fail Safe is enabled, items for setting the throttle servo posi-
tion are displayed. The setting method is the same as "Stick sw", so please
refer to this section of the manual for information on setting this function.
(8) BAT F/S: Battery fail safe
When the receiver battery voltage becomes equal to or less than "BFS.
Volt" set in the "GOV EXPERT" menu, the battery fail safe function is acti-
vated, the governor function is turned OFF, and the throttle servo moves to
the set position.
If the battery voltage is lower than the set voltage of the
"
Battery F/
S
"
for about 3 seconds, the Gx (gyro) LED of the CGY solid red light.
When
"
Battery F/S
"
is set to
"
ACT
"
in
"
GOV BASIC
"
, the servo is fixed
to the throttle position set by
"
Battery F/S
"
. When the throttle stick is
set to the slowest position, the
"
Battery F/S
"
function is temporarily
canceled. However, after 30 seconds, the
"
Battery F/S
"
function is
activated again and the servo is locked. When the
"
Battery F/S
"
oper-
ates, quickly landing and stopping the helicopter, please charge the
battery.
WARNING
When using the CGY for the first time, or when making changes in
the throw of a servo and its linkage, always perform the limit setting
operation.
WARNING
When using the CGY for the first time, or when making changes in
the throw of a servo and its linkage, always perform the limit setting
operation.
(9) Lim. set: Servo limit point setting
Servo limit point setting defines the overall travel range for the throttle ser-
vo. It is fundamental for governor operation and must be set prior to other
functions. Servo limits must also be reset when the throttle linkage or trim
are changed.
How to set the servo limit point:
Set the transmitter's throttle stick to the idle position. Select [Lim. Set Id].
"Sure?" Is displayed. If you touch the [Yes] button. The limit of idle will be
saved to the CGY. The cursor will move to "Lim. Set Hi". Set the stick to the
full high position and set the same as "Lim. Set Id". If the setting data is not
normal (servo operation amount is 50% or less), "Err" is displayed. In this
case, check the transmitter setting and repeat this procedure once again.
(10) Limit Test: Check the set limit point
Check the set limit point. Press "Idle" or "High" to move the servo to each
limit point. Press “End” to end the test.