b)  In  the  case  of  the  non-locking

function,  the  spring  pulls  the
 locking  bar  towards  the  button.
Depending  on  the  desired  func-
tion,  the  spring  is  screwed  into
the fastening bore to the right or
to  the  left  of  the  locking  bar,
along with the fastening screw.

In  order  to  modify  the  device  by
changing to one of these varieties,
you  will  have  to  loosen  the  faste-
ning  screw  of  the  spring,  push  the
spring to the side that corresponds
with  the  desired  function,  and
fasten  the  spring  with  the  screw
again.  Then  mount  the  cover  and
close  the  door  according  to  the
des cription.

Care and maintenance

The fire alarm is maintenance-free.
Still,  if  the  operating  area  is  highly
contaminated  by  dust,  fat,  oil  etc.,
the device should be cleaned from

time  to  time.  Use  a  moist  cloth  to
dust off the device.

Maintaining good working order

In  order  to  maintain  the  operability
of  the  fire  alarm,  the  device  must
be checked for visual damage from
time to time. 
Although the device is being manu-
factured  for  use  in  rough  industry
environments,  it  is  possible  that
damage  could  ensue  due  to  the
impact of for instance heavy strikes
or  blows,  and  that  this could  put
restrictions  on  a  function  or  reduce
tightness.  Defective  parts  may be
replaced by original parts only. The
place and kind of fastening must be
vibration free, in accordance with EN
12094-3.

Manual triggering and 
stop device

The  design  of  the  device  is  to  a
great  extent  identical  with  that  of

the  fire  alarm.  The  device  version
however, does not come in red, but
in  yellow  or  blue.  Operation  is
customer   specific and  has  to  be
agreed  on  with  the  company  fire
brigade or the responsible fire pre-
vention authorities.
The  manual  triggering  and  stop
device  according  to  EN 12094-3
has  been  designed  to  control
 extinguishing systems.
In  all  other  regards,  the  operating
manual  is  valid  for  the  special
alarm, too.

Recycling

The  device  may  be  completely
recycled as electronic waste.
When  the  device  is  disassembled,
plastics, metals and electronics are
to be disposed of separately.
In  every  single  case  the  national
requirements  and  regulations  for
waste disposal must be observed.

Technical Specifications

Type 

2014/2 and 2014/2-GLU

Device name

Fire alarm Type B according to EN 54-11 
or manual triggering and stop device according to EN 12094-3  

Housing

Fibre-reinforced polyester

Housing colour 

Fire alarm:

Red RAL 3000

Manual triggering: yellow RAL 1021
Stop device:

blue RAL 5015

Surface resistance 

Electrostatically conductive

Cable gland 

1x M16 x 1.5 mm

Blind plug 

1x M16 x 1.5 mm

Storage temperature

-60°C to +85°C

Switch contact 

Type 366 (two-way-switch, embedded), II 2 G Ex d II C

Switch reliable load 

max. 1 A / 250 VAC 0.25 A / 250 VDC

Operating utilization position 

Wall mounting only

Operating conditions 

Indoors or outdoors

Connecting terminals 

Up to 4 mm

2

fine-wired or multiwired

Dimensions 

Approx. 136 x 138 x 88 mm

Weight 

Approx. 1.8 kg

Expl. protection class

II and III (no bonding conductor necessary)

Protection degree 

IP 66 (according to IEC 529/EN 60529)

Ex-certificate

Fire alarm / Manual triggering and stop device PTB 97 ATEX 3197

Manual fire alarm device for fire alarm systems

VdS approval

Manual fire alarm device

G 297060

VdS certificate

Manual fire alarm device

0786-CPD-20367

Manual triggering solution for gas extinguishing systems

VdS approval

Manual triggering solution

G 207146

VdS certificate

Manual triggering solution

0786-CPD-20346

Stop device for gas extinguishing systems

VdS approval

Stop device

G 210019

VdS certificate

Stop device

0786-CPD-20944

Designs

Type of protection

Ambient operating temperature

- with module and push button

II 2 G Ex d e mb IIC T6 Gb

-55°C

Ta

+65°C

- with module and push button

II 2 G Ex d e mb IIC T5 Gb

-55°C

Ta

+70°C

- without module, with push button

II 2 G Ex d e IIC T5 Gb

-55°C

Ta

+70°C

- all designs

II 2 D Ex tb IIIC T100°C Db IP66

5

Summary of Contents for 2014/2

Page 1: ...onstruktion zertifiziert nach Verordnung EU Nr 305 2011 für Bauprodukte FHF BA 2013 1 01 16 1 Abb Fig 1 Abmessungen Dimensions 88 136 155 75 138 Befestigungsmaße Fastening measurements Areas of Zones 1 and 2 21 and 22 Class II and III IP 66 IEC 60529 degree of protection Temperature range 55ºC to 70ºC or 65ºC Plastic housing Fibre reinforced polyester All metal parts consist of stainless steel V4A...

Page 2: ...bisolieren und durch Druckschrau be und Kabelverschraubung führen Einzeladern an den Enden ca 5 6 mm abisolieren damit ein sicherer Kontakt gewährleistet ist Die Verdrahtung im Inneren des Anschlussraumes darf nicht an das Verriegelungsystem des Knopfes gelangen damit eine Verrastung sichergestellt ist Die Aderisolation der Leiter muss soweit an der Anschlussklemme liegen dass zwischen den leitfäh...

Page 3: ...je nach gewünschter Funktion rechts oder links vom Verriege lungstab in die Befestigungs bohrung geschraubt Soll ein Umbau in eine der beiden Varianten gewünscht werden so wird die Befestigungsschraube der Feder gelöst die Feder zur ent sprechenden Seite gelegt und mittels Schraube wieder befestigt Anschließend Deckel montieren und Tür wie beschrieben schließen Wartung und Pflege Der Feuermelder i...

Page 4: ... the ter minal room and guide it through the pressure screw and the cable gland Remove approx 5 6 mm of the isolation from the end of the conductors in order to establish good electrical contact The wiring on the inside of the terminal room must not reach the locking system of the button in order to ensure the locking system works properly The conductor isolation of the cable must extend so far to...

Page 5: ... valid for the special alarm too Recycling The device may be completely recycled as electronic waste When the device is disassembled plastics metals and electronics are to be disposed of separately In every single case the national requirements and regulations for waste disposal must be observed Technical Specifications Type 2014 2 and 2014 2 GLU Device name Fire alarm Type B according to EN 54 11...

Page 6: ...king diagram 6 Abb Fig 2 Anschluss klemmen Connecting terminals Anschluss raum Terminal room Modul Module Schalter Switch Anschlussplan Wiring diagram Abb Fig 3 Brand melde leitung Fire alarm cable Verschraubung Cable gland Druckschraube Pressure screw Kabeleinführung Cable gland ...

Page 7: ...7 ...

Page 8: ...8 ...

Page 9: ...9 ...

Page 10: ...ner Instandsetzung oder einem Austausch des Gerätes muss es von der Spannungs versorgung getrennt werden Wenn eine Wartung oder eine Reparatur unter Spannung un vermeidbar ist darf das nur von einem unterwiesenen Fachmann geschehen 8 Die vorgeschriebene Gebrauchslage ist zu berücksichtigen 9 Das Wechseln oder Ergänzen von Modulen darf nur von einem Fachmann durchgeführt werden Es sind nur Module z...

Page 11: ... may cause damage 7 Before the device is repaired or replaced it must be disconnected from the power supply If the maintenance or repair of a live device cannot be avoided this must be done by authorised personnel only 8 Take into consideration the required operating position 9 Replacing or amending modules must be carried out by a trained technician only Use only modules that are certified for in...

Page 12: ... 45478 Mülheim an der Ruhr Web www fhf de Phone 49 208 8268 0 Fax 49 208 8268 286 Mail info fhf de Orders fhf orders eaton com Requests fhf sales eaton com Support fhf support eaton com Änderungen und Irrtum vorbehalten Subject to alterations or errors ...

Reviews: