7 FUNCTIONS WITH FACILITATED ACCESS

7.1 Register of minimum and maximum temperatures

Press       , appear the minimum registered temperatures. Soon will apears the the maximum registered 
temperature.

Note:

 To reset the registers, keep the key       pressed during the visualization of minimum and maximum 

registers until            to be showed.

 - 

 - 

 - 

7.2 Viewing current date and time:

You can press the        key shortly to view the date and time set in the controller. The display 
shows the current day, month, year, hours and minutes, in this order. 
Ex: 03/17/2006 12h43min 

F22 - Delay to enable the alarm when the instrument is powered on

During  this  time  the  alarm  is  kept  turned  off  waiting  that  the  system  reaches  the  working  control 
temperature (only if F17= 4,5 or 6).

F23 -Reactivation time of alarm when inhibited manually

This function allows three different settings (only if F17= 4,5 or 6):

  

-

 

The alarm is inhibited by an indefinite period or until the temperature range in normal 

working condition and return the alarm again;

      

-

 

The alarm can not be inhibited by facilitating access keys;

                 

 to

-

 

The alarm will be inhibited during this period (in minutes), returning the call if the 

alarm condition persists;

F24 - Alarm time (on cycle)

It allows to adust the time that OUT3 output will keep turned on (only if F17= 4,5 or 6).

F25 - Alarm time (off cycle)

It allows to adust the time that OUT3 output will keep turned off (only if F17= 4,5 or 6).

 

 

F26 - Enables

 

F24 and F25

 

on

 

easy access

 

menu

Enables the time setting alarm ON and OFF in the easy access

 

menu, if the 3rd stage is configured as an 

alarm (F17=4, 5 or 6).

- Disabled
- Enabled

F27 -Operation mode of Buzzer

 

- Intra-range alarm (F28 and F29)
- Extra-range alarm (F28 and F29)

 

- Extra-range alarm relative to the 1st stage setpoint (           - F28 and           + F29), It is 
considered the absolute values of F28 and F29)

F28 - Acting point of Buzzer (inferior limit)

It is the inferior value of temperature to the buzzer alarm act as the configured Operation Mode of Buzzer 
(F27).

F29 - Acting point of Buzzer (superior limit)

It is the superior value of temperature to the buzzer alarm act as the configured Operation Mode of 
Buzzer (F27).

F30 - Buzzer time on

It is the time that the Buzzer will be turned on (cycle on). To turn it off the sonore alarm (Buzzer) adjust the 
value “0” to this function.

F31 - Buzzer time off

It is the time that the buzzer will be turned off (cycle off). To turn it off the sonore alarm (Buzzer) adjust the 
value “0” to this function.

F32 - Inhibition time of Buzzer during electrical supply

 It is the time were the alarm will kept turned off even if in alarm contitions. 
It serves to inhibit the buzzer during the time while the system do not reaches the working control 
temperature.

 

F33 -Reactivation time of Buzzer when inhibited manually

This function allows three different settings:

  

-

 

The Buzzer is inhibited by an indefinite period or until the temperature range in normal 

working condition and return the alarm again;

      

-

 

The Buzzer can not be inhibited by facilitating access keys;

                 

to

             

The Buzzer will be inhibited during this period (in minutes), returning the call if the 

alarm condition persists

.

-

F34 - Time for the open door alarm

 

When the door open alarm is enabled, the buzzer will be triggered after the door has been left open for 

the programmed amount of time. The time the buzzer is on and off is set with F30 and F31.

     

- Disabled

    to

           

- Minutes to activate the open door alarm

F35 - Digital input operation mode

This function allows to configure what status of digital input will indicate that the door is open:

- Closed contact indicates that the door is open

- Open contact indicates that the door is open

F36 - Datalogger operation mode 

Allows to choose between the following operation modes of the datalogger:

- Always OFF
- Always ON
- Manual operation

     

               

F37 - Datalogger sampling interval 

Time period in which the controller will register a sample of the temperature and the control outputs 
status.

F38 - Variation of the temperature to force data recording 

Temperature difference to forces the recording of data in the memory, independently of the sampling 
time  configured  at  F37.  To  desable  this  function,  just  decrease  the  value  until  the            message                       
appears in the display.

F39 - Variation of the outputs to force data recording 

Indicates whether the change in the control outputs (configured as cooling or heating) will force the 
recording of data in memory regardless of the time of sampling set in F37. Data recording will also occur 
if the device enters or exits the alarm condition (for OUT3 and buzzer) and lack of and return electricity  
(if the battery is connected as described on item 10.1)

- OFF
- ON

F40 - Overwrite records in the memory when it is full 

This function indicates whether the controller  should start writing the new data at the beginning of the 
datalogger's memory when it is full. This prevents that the latest data recorded from controller be erased 
first. 

F41 - Intensity of the digital filter 

This filter aims at simulating an increase of the mass of sensor , thus increasing its response time 
(thermal inertia). The larger the value adjusted in this function, the longest the response time of sensor.

A typical application requiring this filter is the freezer for ice cream or frozen goods, because when the 
door is opened a hot air mass reaches the sensor directly, causing the indication of the measured 
temperature to rise quickly and the compressor to be activated unnecessarily.

F42 - Network address RS - 485 

Each controller connected to the RS-485 network must have its own address different from the others so 
that the computer will be able to identify it.

Attention:

 To avoid communication problems, make sure that there are no controllers with the same 

address.

6.2

Functions

 - 

- To enter the access code
- Advanced setting functions
- Date and time setting

6 - PARAMETERS ALTERATION

6.1 - To enter the function menu

Press        and        simultaneously for 2 seconds to display           and release the keys. When           is 
displayed, press        (shortly), and enter the code (123) through the       and       keys. Press        to 
confirm. Use the       and       keys to access the other functions and proceed the same way to adjust 
them. Press          (long touch) until            is displayed to exit the menu and return to normal operation.

SET

SET

SET

SET

7.3 - Clearing datalogger memory

Press the        and         keys for 2 seconds to display                    . The LCD then displays          . If you 
don't want to clear the memory and cancel the operation press        . To clear the memory press        until
            is displayed and press           to confirm and exit the function.

 - 

With F36 set to value 2 and the        and        keys pressed simultaneously for 10 seconds one can 
enable or disable the operation of data recording (datalogger). The            message will be shown, then  
           when the datalogger is activated and            when it is deactivated. 
If F36 is set to 0 or 1 the messages            and            will be displayed respectively.

 - 

7.4 Manual datalogger activation

7.5 Alarm and Buzzer inhibition 

To inhibit the OUT3 press the          and           keys simultaneously . 
To inhibit the Buzzer press the          and           keys simultaneously.
- The inhibition of alarm and buzzer can be configured by the functions F23 and F33, respectively.

SET

SET

SET

SET

SET

8 - SIGNALING

Invalid parameters configuration

The outputs are turned off automatically in this situation
Please check  which parameters have invalid  data configured and correct them to return to 
normal operation.

 - 

OUT 1 

- Output 1 turn on

OUT 2 

- Output 2 turn on

OUT 3 

- Output 3 turn on

BUZZ 

-  Internal buzzer activated

           

- Detached temperature sensor or outside the specified range.

9 SELECTION OF THE UNIT (ºC / ºF)

In order to define the unit that the instrument will operate in, enter  function          with the access code 
231 and confirm with the           key. Press the         key and the indication            will appear.
 Press         to choose between           or            and confirm. After selecting the unit the            message 
will appear, and the instrument will return to the message           . Every time that the unit is changed, the 
parameters should be reconfigured, since they assume the “standard” values.

- Deprogram clock 

®

- Communication with SITRAD
- Open door
- Alarm of datalogger memory full
- Alarm of datalogger memory corrupted

SET

SET

F21- Minimum delay to turn on the third stage

It is the minimum time that the output OUT3 will keep turned off, it means, the amount of time between 
the last stop and the next start. Only if programmed in F17 = 0, 1, 2 or 3.

6.3 - Adjustment of the date and time

Inside the functions menu, press the key        until the message            appears in the visor.
Hit key          . The settings will appear in the following order:
                            
                

 DAY       MOUTH        YEAR       HOURS      MINUTES      

Ex.: 17/03/2006 12h43min   

SET

- Day
- Month
- Year
- Hours
- Minutes

- Day
- Month
- Year
- Hours
- Minutes