Full Gauge Controls MT-514e Manual Download Page 4

F30 - Output on time in OUT2 alarm status:

F31 - Output off time in OUT2 alarm status:

Selects the cycling time in seconds of the alarm output when it is active. If any of those functions are set 
with a value of 

[,,,0]

 the output will be permanently active.

 

F32 - Open door time for alarm:

If the door remains open for a time equal to, or greater than, the one configured in this parameter, the 
controller will set off a visual open door alarm 

[AOPn]

 and the audible alarm (Buzzer).

The alarms are suspended upon the door closing. The audible alarm may be inhibited through the 

>

 

key (pressed for 2s). This function can be switched off by setting it at the minimum value 0 

[no,,]

.

Note 1:

 In order for the open door alarm to operate, the function “Digital input operating mode” 

[,F29]

 

must be configured as open door contact.
The audible alarm is activated only if the buzzer is enabled in the function “Enable Buzzer (0-Disabled 
/1-Enabled)” 

[,F28]

.

Note 2:

 If the function “Digital input operating mode” 

[,F29]

 is configured as open door contact, the 

open door indication 

[OPEn]

 will be displayed every time the door is open, except for the cases of 

alarm.

F33 - Operating mode of the digital filter:

[,,,0]

- The filter acts both on the rise as on the decrease temperature.

[,,,1]

- The filter acts only in the temperature rise ramp. When the temperature falls, your response 

will be immediate.

F34 - Digital filter intensity applied to the sensor:

This filter has the purpose of simulating increase in thermal mass at the sensor thereby increasing its 
response time (thermal inertia). The higher the value set in this function, the more time the sensor takes 
to respond.
This function can be switched off by setting it at the minimum value 0

[no,,]

F35 - Functions lockdown:

This allows and configures the functions lockdown.

[,,,0]

- Do not allow the functions lockdown.

[,,,1]

- Allow a partial lockdown where the control functions will be locked but the adjustment of the 

setpoint, manual defrost, and maximum and minimum record are allowed.

[,,,2]

-  Allow  the  full  lockdown,  enabling  only  the  manual  defrost  and  maximum  and  minimum 

record.

F36 - Time for functions lockdown:

Allow lockdown of control functions (see item 6.3.3).

[,,15]

 - 

[,,60]

 Defines the time in seconds for the controller to activate.

F37 - Control functions shutdown:

Allow control functions shutdown (see item 6.3.4).

[,,,0]

- Disables the control functions shutdown.

[,,,1]

- Enables activation/deactivation of the control functions only if the functions are unlocked.

[,,,2]

- Enables  activation/deactivation of the control functions even if the functions are locked.

Control functions off.

Contact Full Gauge Controls.

Reconfigure the values of the functions.

8. OPTIONAL ITEMS - Sold Separately

Ecase

It is recommended for the Evolution line, keeps water from entering the back part of the instrument. It 
also protects the product when the installation site is washed.

Extension Frame

The Full Gauge Controls extension frame allows the installation of Evolution / Ri line with measures 
76x34x77  mm  (dimensions  of  the  clipping  for  fixing  in  the  extension  frame  is  71x29mm)  in  varied 
situations, since it eliminates precision cut to embed the instrument. Allows customization via a sticker with 
the brand and the company contact, and accompany two 10A (250 Vac) switches that can trigger internal 
light, air curtain, on / off system or fan.

[OFF,]

[eCAL]

[pppp]

7. SIGNALS

Error in sensor: Sensor disconnected or damaged.

Manual activation of defrost process.

Manual activation of end of defrost process.

[Err1] 

[Defr][On,,] 

[defr][Off,]

Low temperature alarm.

[Atlo]

[Athi]

[ALrC]

High temperature alarm.

Compressor reached maximum time on limit without reaching SP.

[LOC,][On,,]

[LOC,][OFF,]

[inib] 

[AVoL]

[AOPn]

[OpEn]

Power outage alarm indication.

Open door alarm indication.

Open door indication.

Functions lockdown.

Unlocking of functions.

Buzzer inhibited.

Electrical noise suppressing filter

Contact suppressor connection 

diagram

A1

A2

A1 and A2 are the
contactor coils.

Diagram for suppressor installation 

for direct drive load inputs

Load

Suppressor

For  direct  activation  the 
maximum specified current 
should  be  taken  into 
consideration.

RC FILTER

Example of connections for detecting open door and power outage:

This configuration may be used to detect power outage alarm (115/230 V AC) and also to detect that the 
door has been left open (either one event).
In those configurations, the messages 

[AVoL]

 and 

[AOPn]

are displayed alternately when alarm 

event is detected (power outage or open door alarm).
For this purpose, the user may use the pushbuttons (not supplied) and a contactor or auxiliary contact 
(not supplied) connected in series or in parallel, as shown in examples below:

F29 =

[,,,6]

1

5 6 7 8

2 3 4

SENSOR

NO

NO

Vca

A1

A2

Connection in series

NO

Door contact

F29 =

[,,,5]

1

5 6 7 8

2 3 4

SENSOR

NC

NC

Vca

A1

A2

Connection in parallel

NC

Door contact

F29 =

[,,,3]

F29 =

[,,,4]

1

5 6 7 8

2 3 4

SENSOR

NC

NC

Vca

A1

A2

1

5 6 7 8

2 3 4

SENSOR

NO

NO

Vca

A1

A2

Examples of connection for power outage detection:

This  configuration  may  be  used  when 

  is  being  energized  by  a  12/24  V  DC  battery 

(common in vaccine refrigerators) and one wants to detect when a power outage occurred (115/230 V 
AC). In this configuration, the message

[AVoL]

 is displayed when alarm is detected for power outage. 

To  that  end,  the  user  may  utilize  a  contactor  or  auxiliary  contact  (not  supplied),  where  NC 
(F29=

[,,,3]

) or NO (F29=

[,,,4]

) contacts are connected to the digital input and contacts A1 and 

A2 (contactor coil) are connected to the power system, as shown in examples below:

MT-514

e

 

 - version 2 or higher

EasyProg

It is an accessory that has as its main function to store the parameters of the controllers. At any time, you 
can load new parameters of a controller and unload them on a production line (of the same controller), 
for example. It has three types of connections to load or unload the parameters:

- Serial RS-485:

 It connects via RS-485 network to the controller (only 

for controllers that have RS-485). 

- USB:

 it can be connected to the computer via the USB port, using 

Sitrad's Recipe Editor.

-  Serial  TTL: 

The  controller  can  be  connected  directly  to 

EasyProg 

by the TTL Serial connection.

EASYPROG

Suppressor

Summary of Contents for MT-514e

Page 1: ...arm ALRM DEFR COMMON NO NC REFR HEAT NO NC COMMON COMMON 6 OPERATIONS 6 1 Quick Access Menu Map To access or browse in the quick access menu use the key quick touch while the temperature is being displayed by the controller Each touch displays the next function of the list for confirming use the key quicktouch Forfurtherdetails refertochapter6 3 REFR HEAT NO NC REFR HEAT NO NC COMMON COMMON Loads ...

Page 2: ...nfirmwith Forchangingtheotherfunctions browsethe menu through the keys and proceed the same way in order to adjust them To exit the menu andreturntothenormaloperation press longtouch until isdisplayed OBS If the functions lockdown is enabled when pressing the keys the controller will display themessage LOC andwillnotallowparameteradjustment and or or or 6 5 Parameters table Legend yes yes no no Of...

Page 3: ...tatuswiththesensordamaged Ifthesensorisinshort circuited offoroutofthemeasurerange thecompressorassumesthesetstatus inthisfunction 0 Compressoroff 1 Compressoron 2 Cyclingaccordingtotimesdefinedin F21 and F22 Note Ifintheheatingmode andinerror theoutputwillbeswitchedoff F21 Compressortimeonincaseoferror F22 Compressortimeoffincaseoferror These determine the minimum time the compressor will remain ...

Page 4: ... the clipping for fixing in the extension frame is 71x29mm in varied situations sinceiteliminatesprecisioncuttoembedtheinstrument Allowscustomizationviaastickerwith the brand and the company contact and accompany two 10A 250 Vac switches that can trigger internal light aircurtain on offsystemorfan OFF eCAL pppp 7 SIGNALS Error in sensor Sensor disconnected or damaged Manual activation of defrost p...

Page 5: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...

Reviews: