Full Gauge Controls MT-514e Manual Download Page 3

F03 - Using Presets:

Allows configuration of the controller so as whether or not to use the presets:

[no,,]

- No:

 If configured this way, the instrument will not use the preset values in the control routines. 

For this purpose, the setpoint

[SP,,]

 will be used, adjusted via the quick access menu. The control 

differential to be used shall be the same as in preset

 [rc1,]

, F06 “OUT1 output control differential 

(

[rc1,]

)”. The cooling time to be used shall be the same as in preset 

[rc1,]

, F07 “OUT1 output 

cooling time (

[rc1,]

)”. Defrost time to be used will be the same as in preset 1, F08 “OUT1 output 

defrost time (

[rc1,]

)”.

The value configured in 

[SP,,]

 may be adjusted between F13 “Minimum setpoint allowed to the end 

user” and F14 “Maximum setpoint allowed to the end user”.
In this configuration, the controller will not indicate which preset is enabled.

[yEs,]

- Yes:

 Selection of presets will be made through the quick access menu, in the same way as for 

adjusting the setpoint. In this configuration, the controller will indicate in the display which preset is 
enabled, 

[rc1,]

 or 

[rc2,]

. If configured this way, in the control routines the instrument will use the 

values of setpoint, control differential, cooling time and defrost time configured in the parameters table.

F04 - Output operating mode OUT1:

Selects the out1 output operating mode:

[,,,0]

- Cooling

[,,,1]

- Heating

F05 - Operation setpoint (

): 

It is the reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment when preset (

[rc1,]

) is used.

F06 - Control differential (Hysteresis) (

):

It is the difference in temperature (hysteresis) between TURNING ON and OFF the cooling (or heating) 
when recipe (

[rc1,]

) is used.

Example:

 One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 

cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0).

F07 - Cooling time (interval between defrosts)  (

):

Corresponds to the time the controller will act on cooling when preset (

), is used; following this 

period, the controller enters the natural defrost process.

F08 - Defrost time (

): 

It is the defrost duration time when preset (

) is used. Within this period, the relay will remain off; 

following this period, the controller will then return to the cooling state.

F09 - Operation setpoint  (

): 

It is the reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment when preset (

) is used.

F10 - Control differential (Hysteresis) (

[rc2,]

):

It is the difference in temperature (hysteresis) between TURNING ON and OFF the cooling (or heating) 
when preset (

[rc2,]

) is used.

Example:

 One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 

cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0).

F11 - Cooling time (interval between defrosts) (

[rc2,]

):

Corresponds to the time the controller will act on cooling when recipe (

[rc2,]

) is used; following this 

period, the controller enters the natural defrost process.

F12 - Defrost time (

[rc2,]

):

It is the defrost duration time when preset (

[rc2,]

) is used. Within this period, the relay will remain off; 

at the end of this period, the controller will return to the cooling state.

F13 - Minimum setpoint allowed to the end user:

Avoids regulation of excessively low setpoint temperatures by mistake.

F14 - Maximum setpoint allowed to the end user:

Avoids regulation of excessively high setpoint temperatures by mistake.

F15 - Minimum OUT1 output time on:

It is the minimum time the compressor will remain on, i.e. the time interval between the last start-up and 
the next stop.

F16 - Minimum OUT1 output time off:

It is the minimum time the compressor will remain off, i.e. the time interval between the last stop and the 
next start-up. It is used to relieve the discharge pressure and increase the service life of compressor.

F17 - Initial status when energizing the instrument:

It allows  defrosting when controller is energized such as, for example, upon resuming of electric power 
(in the event of power outage).

[,,,0]

- Cooling

[,,,1]

- Defrost

F18 - Temperature indication locked during defrost:

If 

[,F18]

 is enabled, the indication will only be released at the next cooling cycle after the temperature 

reaches the “locked” value again, or after 15 minutes in cooling (as a safety measure).

F19 - Instrument energization delay:

This function being enabled, when the instrument is energized it only works as temperature indicator 
remaining with the output off during the defined time. In installations with several units of equipment, 
configuring different values for the delay time in the start-up of each instrument, it is possible to avoid 
peaks of demand by activating the loads at different times.
This delay may be of the compressor or of defrost (when defrost is configured at the start).

Note:

 At its end, the count of minimum time of output off is started, if there is any.

[Rc1,]

[Rc1,]

[Rc1,]

[Rc1,]

[Rc1,]

[Rc1,]

[Rc2,]

[Rc2,]

Temperature [°C]

Setpoint

Cooling

Se Hysteresis

Time [S]

Relay Off

Relay On

4°C

5°C

Temperature [°C]

Setpoint

Heating

Setpoint - Hysteresis

Time [S]

4°C

5°C

Relay Off

Relay On

F20 - Compressor status with the sensor damaged:

If the sensor is in short-circuited, off or out of the measure range, the compressor assumes the set status 
in this function.

[,,,0]

- Compressor off

[,,,1]

- Compressor on

[,,,2]

- Cycling according to times defined in 

[,F21]

 and 

[,F22]

Note:

 If in the heating mode, and in error, the output will be switched off.

F21 - Compressor time on in case of error:

F22 - Compressor time off in case of error:

These determine the minimum time the compressor will remain on/off, respectively, if the sensor is off or 
out of the measure range.

F23 - Maximum Compressor on without reaching setpoint:

This is the maximum time the compressor may remain on without reaching the setpoint during the 
cooling process for safety reasons. If this time is surpassed, the output is switched off and also the visual 
alarm 

[ALrC]

 and the audible alarm (buzzer) will be activated. This function can be switched off by 

setting it at the minimum value 0 

[no,,]

.

Note:

 In this situation, the controller should be switched off and switched back on so as to continue with 

the operation.

Note 2:

 If the OUT2 output is set up to work differently from the alarm, this will also be switched off for 

safety reasons.

F24 - Low temperature alarm:

The temperature below which the instrument will indicate visual low temperature alarm 

[ALo,]

 and 

the  audible  alarm  (Buzzer).  The  differential  for  alarm  shutdown  is  set  at  0.1  °C/1  °F.  This  alarm 
considers the temperature displayed, thus being influenced by the indication of temperature lockdown 
during defrost 

[,F18]

.

F25 - High temperature alarm:

The temperature above which the instrument indicates high visual temperature alarm 

[Ahi,]

 and the 

audible alarm (Buzzer). The differential for alarm shutdown is set at 0.1 °C/1 °F. This alarm considers 
the temperature displayed, thus being influenced by the indication of temperature lockdown during 
defrost 

[,F18]

.

Note:

 If an alarm event takes place, the OUT1 output is switched off if the controller is operating in 

cooling mode and the alarm triggers for low temperature or the controller is operating in heating mode 
and the alarm triggers for high temperature.

F26 - OUT2 output operating mode:

Selects the OUT2 output operating mode:

[,,,1]

- Absolute  extra-range  alarm:

  Considers  the  values  defined  in

[,F24]

and

[,F25]

as 

minimum and maximum values to activate the alarm output.

[,,,2]

- Extra-range alarm relating to the setpoint:

 Considers the active preset setpoint 

[rc1,]

 

or

 [rc2,]

 and the absolute values defined in 

[,F24]

 and 

[,F25]

, i.e. the positive value of these 

functions as minimum and maximum values to activate the alarm output.

For example:

Desired temperature

[SP,,]

: - 5 °C

Low temperature alarm 

[,F24]

: 2 °C

High temperature alarm 

[,F25]

: 2°C

Limits: (

[SP,,]

 - 

[,F24]

 and 

[SP,,]

[,F25]

).

The low temperature alarm will be signaled at -7°C(-5 -2) and the high temperature alarm at -3°C(-5+2).

[,,,3]

 - Electric defrost (by resistance):

 Where only the OUT2 output is activated during the 

defrost process.

[,,,4]

 - Hot gas defrost:

 Where the OUT1 and OUT2 compressor outputs are activated during the 

defrost process.

[,,,5]

 

- OUT2 output as OUT1 output NC:

 In this option, the OUT2 output is activated when OUT1 

output is deactivated, irrespectively of the state (cooling/heating or defrost), except when the sensor is 
in error 

[,F20]

.

Note: 

If the OUT2 output is configured to work differently from alarm, the indications of absolute alarm 

are still visual (messages in the display) and audible (if the buzzer is enabled).

Note 2:

 If the OUT2 output is configured to work as defrost (electrical or hot gas), after elapsing of 

defrost time a fixed 2-minute time period is counted for drainage. This time is necessary for the dripping, 
i.e. for the last drops of water to run from the evaporator. Within this period, outputs OUT1 and OUT2 
remain off.

F27 -  Alarm inhibition time when energizing the controller:

This is the time during which the alarm remains off even under conditions of alarm during the instrument 
start-up. This time will be counted after elapsing of the time configured in 

[,F19]

. This function can be 

switched off by setting it at the minimum value 0 

[no,,]

.

F28 - Enable buzzer (0-Disabled/1-Enabled):

Allows enabling and disabling of the internal buzzer for alarm signaling.

F29 - Digital input operating mode:

Selects the digital input operating mode.

[no,,]

- Disabled

[,,,1]

- Digital input: Open door (active at the contact closing)

[,,,2]

- Digital input: Open door (active at the contact opening)

[,,,3]

- Digital input: External alarm/power outage (active at the contact closing)

[,,,4]

- Digital input: External alarm/power outage (active at the contact opening)

[,,,5]

- Digital input: Open door and power outage (active at the contact closing)

[,,,6]

- Digital input: Open door and power outage (active at the contact opening)

Examples of connection for detecting open door alarm:

This configuration may be used for the

 

 

to detect whether the door has been left open for a 

time above the value set up in “

[,F32]

 - Time with open door to trigger alarm”. In this configuration, the 

message 

[AOPn]

 is displayed when an open door alarm is detected. To that end, the user may use the 

NO or NC pushbuttons (not supplied) connected to the digital input, as shown in examples below:

MT-514

e

1

5 6 7 8

2 3 4

SENSOR

NC

F29 =

[,,,1]

Door contact

1

5 6 7 8

2 3 4

SENSOR

NO

F29 =

[,,,2]

Door contact

Summary of Contents for MT-514e

Page 1: ...arm ALRM DEFR COMMON NO NC REFR HEAT NO NC COMMON COMMON 6 OPERATIONS 6 1 Quick Access Menu Map To access or browse in the quick access menu use the key quick touch while the temperature is being displayed by the controller Each touch displays the next function of the list for confirming use the key quicktouch Forfurtherdetails refertochapter6 3 REFR HEAT NO NC REFR HEAT NO NC COMMON COMMON Loads ...

Page 2: ...nfirmwith Forchangingtheotherfunctions browsethe menu through the keys and proceed the same way in order to adjust them To exit the menu andreturntothenormaloperation press longtouch until isdisplayed OBS If the functions lockdown is enabled when pressing the keys the controller will display themessage LOC andwillnotallowparameteradjustment and or or or 6 5 Parameters table Legend yes yes no no Of...

Page 3: ...tatuswiththesensordamaged Ifthesensorisinshort circuited offoroutofthemeasurerange thecompressorassumesthesetstatus inthisfunction 0 Compressoroff 1 Compressoron 2 Cyclingaccordingtotimesdefinedin F21 and F22 Note Ifintheheatingmode andinerror theoutputwillbeswitchedoff F21 Compressortimeonincaseoferror F22 Compressortimeoffincaseoferror These determine the minimum time the compressor will remain ...

Page 4: ... the clipping for fixing in the extension frame is 71x29mm in varied situations sinceiteliminatesprecisioncuttoembedtheinstrument Allowscustomizationviaastickerwith the brand and the company contact and accompany two 10A 250 Vac switches that can trigger internal light aircurtain on offsystemorfan OFF eCAL pppp 7 SIGNALS Error in sensor Sensor disconnected or damaged Manual activation of defrost p...

Page 5: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...

Reviews: