MAINTENANCE (cont.)

Checking the engine oil

See 

“Checking the oil”

 section on page 12 of this manual for full details.

Changing the engine oil

It is recommended that SAE 10W-30 (multi-viscosity) 4-stroke engine oils are used 

at temperatures from 5 to 35°C and synthetic oils 5W-30 (multi viscosity) is used 

for temperatures -5 to 5°C.

1. 

Stop the engine.

2.

   Let engine sit and cool for several minutes (allow crankcase pressure to 

equalize).

3.

  Remove the oil access cover (7) to gain access to the oil filler cap.

4. 

Place oil pan (or suitable container) under the oil filler cap.

5.

   Remove oil filler cap. With a damp rag, thoroughly clean around the oil filler 

cap.

6.

   Insert provided funnel (9) around oil fill/drain and carefully tilt the inverter so 

the oil drains down the through the funnel (9) into the container.

7.

  Allow oil to completely drain.

8.

   Fill crankcase with new oil using the provided funnel 

(9) and check the oil level with the dipstick (fig. 17).

9.

  Reinstall the oil access cover (7).

10.

  Please dispose of used motor oil according to local 

regulations. Do not throw it in the trash or pour it on 

the ground.

Air cleaner service

A dirty air cleaner will restrict air flow to the carburettor. To prevent carburettor 

malfunction, service the air cleaner regularly. Service more frequently when operating 

the generator in dust environment.

1.

   Turn off the inverter and let it cool for several minutes if running.

2.

   Remove  the  Routine maintenance cover (6) to gain 

access to the air filter.

3.

   Turn the 2 knobs on the air cleaner to unlock the cover 

(fig. 18). Tip the cover down to access the foam air filter.

4.

  Remove the foam air filter from the air cleaner housing.

5.

   Wash the foam air filter by submerging the filter in a 

solution of household detergent soap and warm water. 

Slowly squeeze the foam to thoroughly clean.

6.

   Rinse in clean water by submerging the foam air filter in fresh water and applying a 

slow squeezing action.

7.

  Dry the air filter element by again applying a slow firm squeezing action.

8. 

Allow the air filter to completely dry.

9.

   Return the air filter element to its position in the air cleaner housing. Install the air 

cleaner cover, making sure the knobs lock into place. Install the routine maintenance 

cover (6).

 

Upper 

level 

allowed

OFF

RUN

CHOKE

91 RON

Unleaded

Petr

ol

Fig. 17

 

Fig. 18

Summary of Contents for SD4000IRS

Page 1: ...follow the warnings and instructions may result in electric shock fire and or serious injury Save all warnings and instructions for future reference 0620 INVERTER GENERATOR 4000W MAX POWER 3500W RUNNI...

Page 2: ...RUN CHOKE 6 Routine maintenance cover 7 Oil access cover 8 AC sockets 9 Funnel 10 Overload indicator LED 11 Output indicator LED 12 Oil alert indicator LED 13 Economy throttle switch 14 DC socket 15 D...

Page 3: ...12V DC 8A 5V DC 2 1A 1 0A AC 240V AC 240V OFF ON AC SW PARALLEL OPERATION OUTLETS OVERLOAD OUTPUT OFF RUN CHOKE ON OFF 4 4 3 KNOW YOUR PRODUCT cont 10 18 17 11 26 21 22 23 24 12 13 20 14 15 19 16 1 3...

Page 4: ...02 INTRODUCTION Page 05 SAFETY INSTRUCTIONS Page 05 EXPLANATION OF RISKS Page 08 PRE OPERATION CHECK Page 12 OPERATION Page 14 MAINTENANCE Page 20 TRANSPORTING STORAGE Page 23 TROUBLE SHOOTING Page 24...

Page 5: ...mage SAFETY INSTRUCTIONS ELECTRICAL SAFETY Read and understand the manual prior to operating this tool Save these instructions and other documents supplied with this tool for future reference The petr...

Page 6: ...m 3ft away from buildings or other equipment during operation ALWAYS operate generator a minimum of 2 meters from any conductive surface eg metals Persons who are fitted with a heart pacemaker or simi...

Page 7: ...ian before connecting the grounding terminal or when using the generator for applications other than direct connection of appliances such as connection to a caravan WARNING The output of this generati...

Page 8: ...well ventilated area Make sure hands are dry before touching unit Placing generator on or against highly conductive surface such as a steel walkway or metal roof Accidental leakage of electrical curre...

Page 9: ...speed has been factory set to provide safe operation Tampering with the engine speed adjustment could result in overheating of attachments and could cause a fire Never attempt to speed up the engine t...

Page 10: ...rator components Contact with hot surfaces such as engines exhaust components could result in serious burns During operation touch only the control surfaces of the generator Keep children away from th...

Page 11: ...peration and controls of the generator Know how to shut it off quickly Equip area of operation with a fire extinguisher certified to handle gasoline or fuel fires Keep children or others away from the...

Page 12: ...ick in the filler hole without screwing it in and then removing it again fig 2 4 If the oil level is below the end of the dipstick refill using funnel 9 until it registers on the halfway mark of the d...

Page 13: ...when refuelling Spilled fuel or fuel vapour may ignite If any fuel is spilled make sure the area is dry before starting the engine WARNING Never refuel the inverter generator while the engine is runni...

Page 14: ...moisture collecting on in or around the generator 1 Turn the engine control switch 5 to the CHOKE position fig 6 2 Hold the generator steady with one hand With the other hand pull slightly on the reco...

Page 15: ...M will increase according to the load applied 2 To run the inverter at maximum power and RPM press the efficiency mode switch to the OFF O position Upper level allowed OFF RUN CHOKE 91 R O N U nl ea d...

Page 16: ...ights the overload indicator LED red 10 may damage the generator Marginal overloading that temporarily lights the overload indicator LED red 10 may shorten the service life of the generator Stop the e...

Page 17: ...rning Fig 13 AC Applications Check the total rating of the appliance to be connected and ensure the rating of the appliance s does not exceed the rating of the inverter generator 1 Make sure the outpu...

Page 18: ...or the battery may occur 2 Connect the charging cable and clamp set 18 plug to DC socket 14 fig 16 The battery will begin charging 3 When disconnecting remove the plug from the inverter generator bef...

Page 19: ...ngine and attached devices run evenly before plugging in the next load Maximum Power in Parallel Operation 7 2kVA Rated Power in Parallel Operation 6 3kVA Limit operation time to 3 seconds for load re...

Page 20: ...ent parts which are not of equivalent quality may damage the generator REGULAR SERVICE PERIOD 1 EACH USE FIRST MONTH OR 20HRS EVERY 3 MONTHS OR 50 HRS EVERY 6 MONTHS OR 100 HRS EVERY YEAR OR 200 HRS I...

Page 21: ...s Do not throw it in the trash or pour it on the ground Air cleaner service A dirty air cleaner will restrict air flow to the carburettor To prevent carburettor malfunction service the air cleaner reg...

Page 22: ...rk plugs To ensure proper engine operation the spark plug must be properly gapped and free of deposits 1 Remove the routine maintenance cover 6 to gain access to the spark plug 2 Take out the spark pl...

Page 23: ...e taken to prepare the inverter for any storage 1 Be sure the storage area is free of excessive humidity and dust 2 Completely drain the fuel from the tank Start the engine and operate it in the idle...

Page 24: ...rter a few times to ensure that fuel enters the carburettor Is the spark plug working Replace spark plug Contact Ozito customer service yes yes yes yes no no no no no no Engine will not start There is...

Page 25: ...after the unit is turned off Exhaust contains poisonous carbon monoxide Do not operate generator in confined area Do not parallel connect other cables to receptacles use special jack or it may cause a...

Page 26: ...facilities exist Check with your local council authority for recycling advice Recycling packaging reduces the need for landfill and raw materials Reuse of recycled material decreases pollution in the...

Page 27: ...s not cover components that have been subjected to operator abuse or negligence To receive full value from the warranty the operator must maintain the inverter generator as instructed in this manual N...

Page 28: ...ilable to you under law The warranty covers manufacturer defects in materials workmanship and finish under normal use 1 YEAR WARRANTY Your product is guaranteed for a period of 12 months from the orig...

Reviews: