background image

En-2

1. SAFETY PRECAUTIONS

1

1.1. IMPORTANT! Please read before starting

This air conditioning system meets strict safety and operating 
standards.
As the installer or service person, it is an important part of 
your job to install or service the system so it operates safely 
and ef

fi

 ciently.

For safe installation and trouble-free operation, you must:

•  Carefully read this instruction booklet before beginning.
•  Follow each installation or repair step exactly as shown.
•  Observe all local, state, and national electrical codes.
•  Pay close attention to all danger, warning, and caution 

notices given in this manual.

WARNING:

 This symbol refers to a hazard or unsafe 

practice which can result in severe personal 
injury or death.

CAUTION:

  This symbol refers to a hazard or unsafe 

practice which can result in personal injury 
and the potential for product or property 
damage.

•  Hazard alerting symbols

 

 Electrical

 

 Safety/alert

If Necessary, Get Help

These instructions are all you need for most installation sites 
and maintenance conditions. If you require help for a special 
problem, contact our sales/service outlet or your certified 
dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper 
installation or maintenance service, including failure to follow 
the instructions in this document.

1.2. SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL 
INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED 
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

•  Do not supply power to the unit until all wiring and tubing 

are completed or reconnected and checked.

•  Highly dangerous electrical voltages are used in this sys-

tem. Carefully refer to the wiring diagram and these instruc-
tions when wiring. Improper connections and inadequate 
grounding can cause accidental injury or death.

•  Ground the unit following local electrical codes.
•  Connect all wiring tightly. Loose wiring may cause overheat-

ing at connection points and a possible 

fi

 re hazard.

When Transporting

Be careful when picking up and moving the indoor and 
outdoor units. Get a partner to help, and bend your knees 
when lifting to reduce strain on your back. Sharp edges or thin 
aluminum 

fi

 ns on the air conditioner can cut your 

fi

 ngers.

When Installing...

...In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit’s 
weight. It may be necessary to construct a strong wood or 
metal frame to provide added support.

...In a Room

Properly insulate any tubing run inside a room to prevent 
“sweating” that can cause dripping and water damage to walls 
and 

fl

 oors.

...In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a 
solid, level foundation for the outdoor unit. This prevents water 
damage and abnormal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal 
frame. 
Provide a suitable air baf

fl

 e.

...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than 
drifting snow.

When Connecting Refrigerant Tubing

•  Keep all tubing runs as short as possible.
• Use the 

fl

 are method for connecting tubing.

•  Apply refrigerant lubricant to the matching surfaces of the 

fl

 are and union tubes before connecting them, then tighten 

the nut with a torque wrench for a leak-free connection.

•  Check carefully for leaks before opening the refrigerant 

valves.

When Servicing

•  Turn the power OFF at the main circuit breaker panel 

before opening the unit to check or repair electrical parts 
and wiring.

•  Keep your fingers and clothing away from any moving 

parts.

•  Clean up the site after you finish, remembering to check 

that no metal scraps or bits of wiring have been left inside 
the unit being serviced.

•  After installation, explain correct operation to the customer, 

using the operating manual.

 DANGER

Never touch electrical components immediately af-
ter the power supply has been turned off. Electrical 
shock may occur. After turning off the power, always 
wait 5 minutes or more before touching electrical 
components.

9318739022_IM.indb   Sec1:2

9318739022_IM.indb   Sec1:2

2010-11-2   15:24:37

2010-11-2   15:24:37

Summary of Contents for Wall Mounted Type

Page 1: ...nection 7 7 ELECTRICAL WIRING 8 7 1 Wiring system diagram 8 7 2 How to the install the indoor unit wire harness 9 7 3 How to connect wiring to the terminals 9 8 FINISHING 10 9 FRONT PANEL REMOVAL AND INSTALLATION 10 9 1 Intake grille removal 10 9 2 Intake grille installation 10 9 3 Front panel removal 10 9 4 Front panel installation 10 10 TEST RUN 11 11 REMOTE CONTROLLER INSTALLATION 11 11 1 Remot...

Page 2: ...ction points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It ma...

Page 3: ...or HFC refrigerant R410A Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 0 004 oz 100ft Do not use copper pipes having a collapsed deformed or discolored portion especially on the interior sur face Otherwise the expansion value or capillary tube may become blocked with contaminants As an air conditioner using R410A incurs p...

Page 4: ...nnect the indoor unit to the outdoor unit 3 1 2 MULTI TYPE INSTALLATION MODEL Diameter Liquid pipe Gas pipe 18 000BTU h model 6 35mm 1 4in 12 70mm 1 2in 24 000BTU h model 6 35mm 1 4in 15 88mm 5 8in CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F Reverse cycle model only In addition if t...

Page 5: ...sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or am...

Page 6: ...ntally and vertically 6 5 Forming the drain hose and pipe Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tape For Left rear piping Left piping...

Page 7: ...with tape to prevent dust dirt or water from entering the pipes Pipe Check if L is flared uniformly and is not cracked or scratched Die L Pipe outside diameter mm in Dimension A mm in Dimension B 0 0 4 mm in Flare tool for R410A clutch type 6 35 1 4 0 to 0 5 0 to 0 020 9 1 11 32 9 52 3 8 13 2 17 32 12 70 1 2 16 6 21 32 15 88 5 8 19 7 25 32 19 05 3 4 24 0 15 16 When using conventional flare tools t...

Page 8: ...oor unit is necessary to connect the indoor unit to the out door unit SINGLE TYPE INSTALLATION MODEL ADAPTER Liquid pipe Gas pipe 18 000BTU h model Use Use 24 000BTU h model Use No use MULTI TYPE INSTALLATION MODEL ADAPTER Liquid pipe Gas pipe 18 000BTU h model No use No use 24 000BTU h model No use No use When the flare nut is tightened properly by your hand hold the body side coupling with a wre...

Page 9: ... the terminal screws Do not use a screwdriver that is too small other wise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table below for the terminal screw tightening torques Tightening torque N m lbf in M4 screw 1 2 to 1 8 11 to 16 CAUTION Match the terminal block numbers a...

Page 10: ...pipe heat insulation Wrap with cloth tape Pipe Drain hose Cloth tape Left piping Connection cable Pipe Drain hose For connection from the left rear Connection cable Wall pipe Connection pipe Drain hose Check the following GOOD Lifted up Saddle Wave End in water NO GOOD NO GOOD NO GOOD Drain hose 1 9 FRONT PANEL REMOVAL AND INSTALLATION 9 1 Intake grille removal 1 Open the intake grille 2 Pull down...

Page 11: ...amp will simultaneously flash slowly Using the wired remote controller Option For the operation method refer to the operating manual 1 Stop the air conditioner operation 2 Press the master control button and the fan control button simultaneously for 2 seconds or more to start the test run 3 Press the start stop button to stop the test run Transmitter section Test run button Test run display 11 REM...

Page 12: ...remote controller CAUTION Before installing be sure to disconnect all power supply Don t touch the heat exchanger During installing or removing operation be sure not to have wire caught by parts or pull it hard Avoid place in direct sunlight Select placing that will not be affected by the heat from a stove etc Before setting up the optional kit please confirm whether air conditioner can receive th...

Page 13: ...ire of external kit with the binder 1 12 6 Front panel control box cover and display case installation Install front panel control box cover and display case by the reverse procedures as stated in 12 4 Front panel control box cover and display case removal external connect wire conduit holder screw binder clamp original wire of control box external connect wire binder clamp screw binder screw cabl...

Page 14: ...SETTING Perform the FUNCTION SETTING according to the installation conditions using the remote controller CAUTION Confirm whether the wiring work for Outdoor unit or Branch box has been finished Confirm that the cover for the electrical enclosure on the outdoor unit is in place This procedure changes to the function settings used to control the indoor unit according to the installation conditions ...

Page 15: ...mote controller The following settings are needed when using the wired remote controller temperature sensor Factory setting Setting Description Function Number Setting Value No 42 00 Yes 01 If setting value is 00 Room temperature is controlled by the indoor unit tempera ture sensor If setting value is 01 Room temperature is controlled by either indoor unit tem perature sensor or remote controller ...

Page 16: ...ge error stoppage permanently Voltage error can restore Over current protected operation stoppage permanently PFC hardware error 6 5 Outdoor unit IPM error Trip terminal L error 6 10 Outdoor unit Display panel error Microcomputers communication error 7 1 Outdoor unit Discharge thermistor error Discharge thermistor 1 error 7 2 Outdoor unit Compressor thermistor error Compressor thermistor 1 error 7...

Page 17: ...g manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 9318739022_IM indb Sec1 17 9318739022_IM indb Sec1 17 2010 11 2 15 25 28 2010 11 2 15 25 28 ...

Page 18: ...9318739022_IM indb Sec1 18 9318739022_IM indb Sec1 18 2010 11 2 15 25 28 2010 11 2 15 25 28 ...

Reviews: