background image

 5

1. PREPARING  INDOOR  UNIT  INSTALLATION

INSTALLATION PROCEDURE

1. REMOVE THE INTAKE GRILLE

Open the intake grille and remove the three screws.
(Fig. 4)

2.  INDOOR  UNIT  INSTALLATION

A. FLOOR CONSOLE TYPE

1. DRILLING FOR PIPING

Select piping and drain directions. (Fig. 5)

The piping and drain can be made in three directions a
shown below.

2. INSTALLING DRAIN HOSE

INSTALL THE DRAIN HOSE

Select whether the drain hose will be connected to the
left or right side. (Fig. 6)

Insert the drain hose into drain pan, then secure the
drain hose with a nylon fastener. (Fig. 9)

When installing the set to wall, install the accessory
wall bracket at the position shown in Fig. 8, and
mount the set to it.

The drain hose can be connected to either the left or
right side. (Fig. 6)

When the directions are selected, drill a 4” (10cm) dia.
hole on the wall so that the hole is tilted downward
toward the outdoor for smooth water flow. When the
pipe is led out from the rear, make a hole in Fig. 7, at
the position shown.

Fig. 4

Screw

Tapping screw

Intake grille

Fig. 7

Wall

1/4” (6 mm)

4” (100 mm)

Indoor side

Fig. 6

Drain hose (Left side)

Drain hose (Right side)

Fig. 5

Install the room air conditioner as follows:

Remark : The main unit can be wired before

the indoor unit is installed. Select the
most appropriate installation order.

Outdoor side

Fig. 9

Drain pan

Nylon fastener

Drain hose

Avoid areas where electrical wiring or
conduits are located.
Accidentally cutting a live wire can cause
death or injury.

Fig. 8

4" (10 cm) hole

2" (5 cm) hole

5" (12.5 cm)

4" (10 cm)

26" (65.5 cm)

21" (53 cm)

1-3/4" (4.5 cm)

2-1/2" (6.5 cm)

20" (50 cm)

39" (99 cm)

2-1/2" (6.5 cm)

9-5/8"

(24.5 cm)

Wall bracket

Side of set

Summary of Contents for SPLIT TYPE AIR CONDITIONER

Page 1: ... thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In M...

Page 2: ...1 3 8 9 53 mm dia 5 8 15 88 mm dia Outdoor Unit Indoor Unit Floor console Indoor Unit Outdoor Unit 3 8 9 53 mm dia 5 8 15 88 mm dia Under ceiling Fig 1 A Fig 1 B ...

Page 3: ...anch circuit and provide a special switch and receptacle Do not extend the power cord 3 OPERATING RANGE Cut each pipe to the appropriate length 12 30 cm to 16 40 cm to dampen vibration between units 2 Foamed polyethylene insulation for copper pipes as required to precise length of piping Wall thickness of the insulation should not be less than 5 16 8 mm 3 Use insulated copper wire for field wiring...

Page 4: ...ty Application STANDARD PARTS The following installation parts are furnished Use them as required 1 1 2 4 4 4 2 6 1 1 1 1 1 1 1 Cover plate left Tapping screw ø4 x 10 For positioning the indoor unit For under ceiling type Anchor bolt M12 Spring nut For suspending the indoor unit on the wall Tapping screw ø4 x 20 For fixing the wall bracket Coupler heat insulator large For indoor side pipe joint La...

Page 5: ...rain pipe can be easily installed 7 Take servicing etc into consideration and leave the spaces shown in Fig 2 Also install the unit where the filter can be removed 2 OUTDOOR UNIT 1 If possible do not install the unit where it will be exposed to direct sunlight If necessary install a blind that does not interfere with the air flow 2 Install the outdoor unit in a place where it will be free from bei...

Page 6: ... either the left or right side Fig 6 When the directions are selected drill a 4 10cm dia hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow When the pipe is led out from the rear make a hole in Fig 7 at the position shown Fig 4 Screw Tapping screw Intake grille Fig 7 Wall 1 4 6 mm 4 100 mm Indoor side Fig 6 Drain hose Left side Drain hose Right side Fig 5...

Page 7: ...ide is too high Height A should be less than 5 mm Fig 12 Install the drain hose at the rear it should not be installed on the top or right side B UNDER CEILING TYPE Using the installation template drill holes for piping and anchor bolts for holes Fig 13 2 DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS With a concrete drill drill four 1 2 12 7 mm dia holes Fig 16 Insert the anchor ...

Page 8: ...onnected to the left or right side Fig 6 Insert the drain hose into the drain pan then secure the drain hose with a nylon fastener Fig 9 Wrap the insulation drain hose around the drain hose connection Fig 10 Be sure to arrange the drain hose so that it is leveled lower than the drain hose connecting port to the indoor unit Fig 21 Apply the indoor unit to the brackets Fig 20 Now securely tighten th...

Page 9: ...idth across flats 4 CONNECTING THE PIPING 1 FLARE PROCESSING 1 Cut the connection pipe with pipe cutters so that the pipe is not deformed 2 Holding the pipe downward so that cuttings cannot enter the pipe and remove the burrs 3 Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in Table 3 and insert the flare nut onto the pipe and flare with a flaring tool 4 Chec...

Page 10: ...que Small pipe 22 42 to 25 32 ft lbs 310 to 350 kgf cm Large pipe 54 25 to 57 86 ft lbs 750 to 800 kgf cm Table 4 Flare nut tightening torque Be sure to connect the large pipe after connecting the small pipe completely 4 CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING For both the indoor and outdoor unit sides check the joints for gas leaking by the use of a gas leakage detector without fail when th...

Page 11: ...own the piping before use 2 Add refrigerant from the charging valve after the completion of the work Table 5 25 ft 33 ft 49 ft 66 ft 7 5 m 10 m 15 m 20 m None 2 1 oz 4 2 oz 6 3 oz 60 g 120 g 180 g Pipe length Additional refrigerant 7 HOW TO CONNECT WIRING TO THE TERMINALS A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cut ting pliers then strip the insulation to a...

Page 12: ...r is chafed electric leakage may occur 4 Always connect the ground wire 1 INDOOR UNIT SIDE 1 Remove the electric component box 3 Remove the electric component box cover Remove the three tapping screws Be careful not to pinch the lead wires between the electric component box and base Fig 33 Electric component box Do not remove the screws If the stays are removed the electric component box will fall...

Page 13: ...x must be set as follows Fig 38 Microcomputer SW1 SW1 SW1 Under ceiling type Floor console type 2 OUTDOOR UNIT SIDE A To take off the panel top remove the 2 screws B Dismount the plugs on the conduit plate C Temporarily mount the conduit tubes on the con duit plate D Properly connect both the power supply and inter unit lines to the corresponding terminals on the ter minal board Refer to the wirin...

Page 14: ...l a leakage circuit breaker in accordance with the related laws and regulations and electric com pany standards Short circuit will occur after approx 3 minutes and the power circuit fuse blows Disconnect switch Grounding line Indoor unit Outdoor unit Fig 40 Problem 1 Air conditioner will not operate Compressor will not start only indoor unit will operate Connector trade size for this unit is 1 2 T...

Page 15: ... wall pillar etc with the tapping screw Fig 43 Fig 43 Screws Insert Slide up q Mount the Holder w Set the Remote Control Unit e To remove the Remote Control Unit when use at hand For use as Wall Fixing Type Screws Insert Slide q Mount the Holder w Set the Remote Control Unit e Attach the unit to the holder as shown Screws For use as Handy Type 2 REMOTE CONTROL UNIT CODE SWITCHING If the jumper wir...

Page 16: ...eated TIMER LAMP ON OFF 0 1 sec 0 1 sec 0 1sec ON OFF repeated Error display Error contents Room temperature thermistor abnormal temperature detected OPERATION LAMP ON OFF 0 5 sec 0 5 sec 5 sec Three quick flashes repeated TIMER LAMP ON OFF 0 1 sec 0 1 sec 0 1sec ON OFF repeated Piping thermistor abnormal temperature detected Table 7 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration durin...

Page 17: ... 49 13 MOUNT THE COVER PLATE AND THE INTAKE GRILLE 2 MOUNT THE COVER PLATE LEFT 1 Join the cover plates left and mount with screws 3 MOUNT THE INTAKE GRILLE 1 Cut the right side of the intake grille This is only when the pipe exits from the right side Fig 51 2 Insert the hinges on the bottom of the intake grille into the holes in the base assembly Then mount the arms to the three areas on the top ...

Page 18: ...June 2000 353 Rt 46 W Fairfield NJ 07004 888 888 FGAI www fujitsugeneral com ...

Reviews: