4-3. Swing operation
• To select vertical airflow swing operation
When the swing signal is received, the vertical airflow direction louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode (1 to 3): 1 ↔ 4
• Heating mode/fan mode (4 to 6): 3 ↔ 6
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
• To select horizontal airflow swing operation
No function
4-3. Swing operation
- (04-15) -
4. Louver control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS