![Fujitsu ROG07KPCA Service Manual Download Page 105](http://html.mh-extra.com/html/fujitsu/rog07kpca/rog07kpca_service-manual_2343973105.webp)
Model: ROG12KPCA
Fan speed is defined by outdoor temperature and compressor frequency.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
19
°C
10
°C
0
°C
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry at low outdoor temp.
Y zone
Y zone
Z zone
F zone
G zone
S-HIGH2
—
1,020
—
—
—
—
S-HIGH1
950
1,020
—
—
—
—
HIGH
950
1,020
—
—
—
—
10
—
790
—
—
—
—
9
950
790
950
950
950
950
8
900
790
900
900
350
300
7
900
790
900
900
350
300
6
900
790
900
560
350
300
5
900
730
900
420
320
230
4
800
630
800
350
290
230
3
680
530
680
350
270
230
2
580
470
580
350
270
230
1
540
470
540
350
250
230
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,020 rpm
3-2. Outdoor fan control
- (04-13) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ROG07KPCA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EJ_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 12 16 SR_CH02_AS059EJ_01 ...
Page 31: ...3 TROUBLESHOOTING 2021 12 16 SR_CH03_AS059EJ_01 ...
Page 34: ......
Page 91: ...4 CONTROL AND FUNCTIONS 2021 12 16 SR_CH04_AS059EJ_01 ...
Page 123: ...5 FILED WORKING 2021 12 16 SR_CH05_AS059EJ_01 ...