Environmental temperature
Temperature condition at installed in a cabinet is indicated with ambient temperature measured 3
cm from the disk drive. At designing the system cabinet, consider following points.
•
Make a suitable air flow so that the DE surface temperature does not exceed 55°C.
•
Cool the PCA side especially with air circulation inside the cabinet. Confirm the cooling
effect by measuring temperature of specific ICs and the DE. These measurement results
should be within a criteria listed in Table 4.1.
Table 4.1
Surface temperature check point
No.
Measurement point
Criteria
1
Center of DE cover
55°C
2
Read channel LSI
90°C
3
VCM/SPM Driver
92°C
4
HDC
89°C
5
MPU
88°C
Figure 4.6 Surface temperature measurement points
(5)
Service clearance area
The service clearance area, or the sides which must allow access to the IDD for installation or
maintenance, is shown in Figures 4.7.