- (02 - 05) -
OUTDOOR UNIT
AOU9-12RLS
OUTDOOR UNIT
AOU9-12RLS
2-5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFERENCE
MODEL: AOU9RLS
5m
7.5m
10m
15m
20m
17ft.
25ft.
33ft.
50ft.
67ft.
15m
50ft.
-
-
-
0.877
0.874
10m
33ft.
-
-
0.956
0.891
0.888
7.5m
25ft.
-
0.988
0.960
0.895
0.892
5m
17ft.
1.017
0.992
0.964
0.899
0.895
0m
0ft.
1.025
1.000
0.971
0.906
0.902
-5m
-17ft.
1.025
1.000
0.971
0.906
0.902
-7.5m
-25ft.
-
1.000
0.971
0.906
0.902
-10m
-33ft.
-
-
0.971
0.906
0.902
-15m
-50ft.
-
-
-
0.906
0.902
COOLING
Pipe length
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height difference H
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
5m
7.5m
10m
15m
20m
17ft.
25ft.
33ft.
50ft.
67ft.
15m
50ft.
-
-
-
0.933
0.925
10m
33ft.
-
-
0.981
0.933
0.925
7.5m
25ft.
-
1.000
0.981
0.933
0.925
5m
17ft.
1.017
1.000
0.981
0.933
0.925
0m
0ft.
1.017
1.000
0.981
0.933
0.925
-5m
-17ft.
1.012
0.995
0.976
0.928
0.920
-7.5m
-25ft.
-
0.993
0.974
0.926
0.918
-10m
-33ft.
-
-
0.971
0.923
0.916
-15m
-50ft.
-
-
-
0.914
0.906
HEATING
Pipe length
Height difference H