6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOHG09KMCDN
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
—
—
—
0.904
0.879
10
—
—
0.951
0.919
0.879
7.5
—
0.972
0.955
0.923
0.893
5
0.992
0.975
0.959
0.925
0.897
0
1.000
0.983
0.967
0.933
0.901
Indoor unit is lower than
outdoor unit *2
-5
1.000
0.983
0.967
0.933
0.908
-7.5
—
0.983
0.967
0.933
0.908
-10
—
—
0.967
0.933
0.908
-15
—
—
—
0.933
0.908
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
—
—
—
0.869
0.863
10
—
—
—
0.869
0.863
7.5
—
0.967
0.934
0.869
0.863
5
1.000
0.967
0.934
0.869
0.863
0
1.000
0.967
0.934
0.869
0.863
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.962
0.930
0.864
0.859
-7.5
—
0.960
0.928
0.862
0.856
-10
—
—
0.926
0.860
0.854
-15
—
—
—
0.852
0.846