Preparing to Service Units
Dispensing Gasoline/Ethanol Blends
Page 24 MDE-3893P Encore® and Eclipse® Series Owner’s Manual · December 2011
8
It is recommended that whenever making non-equivalent fuel conversions, all units be
checked for calibration within one month after the fuel conversion.
9
Some non-equivalent fuel conversions must change the pump/dispenser filter type previously
used. For any changes required, consult your ASC or Gilbarco Distributor.
Dispensing Gasoline/Ethanol Blends
The blending option provided on these dispensers is intended for the blending of
Gasoline/ethanol blends designated as E85 with gasoline or gasohol (E10 maximum) to
achieve an intermediate gasoline/ethanol blend.
Standard gasoline or Gasohol (E10 maximum) must not be dispensed through the
same hose as that used for dispensing higher ethanol blend fuels (E11 to E85).
IMPORTANT INFORMATION
Important Requirements for E85 Units
The following equipment and materials are required to properly service the E85 units:
UL-listed E85 Hose (Q13486)
• Veyance
SM
Flexsteel
®
Futura
™
Ethan-All for E85
• Veyance
Flexsteel Futura for E25
Note: Extended Reach hoses not available for the E85 applications.
UL-listed E85 Nozzle (M11298)
OPW 21GE
Note: Approved for use with the E85 dispensers, as required under UL 87A.
UL-listed E85 Swivel (N23748-04)
OPW 241 TPS-0492
Note: Approved for use with E85 dispensers, as required under UL 87A.
UL-listed E85 Shear Valve (T19695-23)
OPW 10P-0152E85
Note: Approved for use with E85 dispensers, as required under UL 87A.
UL-listed E85 Breakaway (N23010-10)
OPW 66V-0492
Note: Approved for use with E85 dispensers, as required under UL 87A.
Filter
Use only filters specifically marked for use with E85.
UL-listed Pipe Sealant
Use only UL-listed TPS PTFE Pipe Sealant manufactured by SAF-T-LOC International Corp.
UL-listed Teflon
®
Tape
Use only UL-listed Taega Technologies Inc. Teflon tape.
Note: Teflon tape must be used only at the inlet pipe connection.