BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
58/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5.3.35 IU_rr_uu_Reset_Filter_Setting (Binary Output Object Type)
Filter sign reset can be commanded for indoor unit.
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Binary Output, 12rruu)
R
R
Object_Name
CharacterString
“IU_rr_uu_
Reset_Filter_Setting
”
R
R
Object_Type
BACnetObjectType
BINARY_OUTPUT (4)
R
R
Present_Value
BACnetBinaryPV
INACTIVE (0) / ACTIVE (1)
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Polarity
BACnetPolarity
NORMAL (0)
R
R
Inactive_Text
CharacterString
"Reset"
O
R
Active_Text
CharacterString
“Not Reset"
O
R
Change_Of_State_Time
BACnetDatetime
-
O
R
Change_Of_State_Count
Unsigned
-
O
R
Time_Of_State_Count_Reset
BACnetDatetime
-
O
R
Elapsed_Active_Time
Unsigned
-
O
R
Time_Of_Active_Time_Reset
BACnetDatetime
-
O
R
Minimum_Off_Time
Unsigned32
-
O
-
Minimum_On_Time
Unsigned32
-
O
-
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
BACnetBinaryPV
INACTIVE (0)
R
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Feedback_Value
BACnetBinaryPV
-
O
W
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured