5 Objects
Supported Object Types
The objects supported are shown in the table below.
Object Type
ID Supported Management Point
Analog-Input
0
IU_rr_uu_SetTemp_Status
IU_rr_uu_SpaceTemp_Status
IU_rr_uu_AutoTempLoLim_Status
IU_rr_uu_AutoTempHiLim_Status
IU_rr_uu_CoolTempLoLim_Status
IU_rr_uu_CoolTempHiLim_Status
IU_rr_uu_HeatTempLoLim_Status
IU_rr_uu_HeatTempHiLim_Status
Analog-Output
1
Batch_SetTemp_Setting
IU_rr_uu_SetTemp_Setting
IU_rr_uu_AutoTempLoLim_Setting
IU_rr_uu_AutoTempHiLim_Setting
IU_rr_uu_CoolTempLoLim_Setting
IU_rr_uu_CoolTempHiLim_Setting
IU_rr_uu_HeatTempLoLim_Setting
IU_rr_uu_HeatTempHiLim_Setting
Analog-Value
2
Averaging
18
Binary-Input
3
Gateway_ES_Status
Gateway_Error_Status
IU_rr_uu_Exists_Status
IU_rr_uu_Operation_Status
IU_rr_uu_ThermostatOFF_Status
IU_rr_uu_FilterSign_Status
IU_rr_uu_Emergency_Status
IU_rr_uu_Error_Status
IU_rr_uu_TempLimValid_Status
OU_rr_uu_Error_Status
OU_rr_uu_ForcedOff_Status
Binary-Output
4
Gateway_ES_Setting
Batch_Operation_Setting
IU_rr_uu_Operation_Setting
IU_rr_uu_ThermostatOFF_Setting
IU_rr_uu_Reset_Filter_Setting
IU_rr_uu_TempLimValid_Setting
OU_rr_uu_ForcedOff_Setting
Binary-Value
5
Calendar
6
Command
7
Device
8
UTY-VBGX
Event-Enrollment
9
File
10
Group
11
Life-Safety-Point
21
Life-Safety-Zone
22
Loop
12
Multistate-Input
13
Gateway_ErrorCode_Status
IU_rr_uu_OperationMode_Status
IU_rr_uu_FanSpeed_Status
IU_rr_uu_AirFlowDirVT_Status
IU_rr_uu_AirFlowDirHZ_Status
IU_rr_uu_RC_Prohibit_Status
IU_rr_uu_ErrorCode_Status