Compressor Temp. Error
OK
OK
OK
OK
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation
failure
, foreign matter on heat exchanger
4. Compressor temperature thermistor
failure
5. Insufficient refrigerant
Compressor temperature thermistor
Compressor temperature thermistor characteristics check
(Check by disconnecting thermistor from PCB)
* For the characteristics of the thermistor, refer to the "Service Parts Information 8.
Check Point 4 : Check the compressor temperature thermistor
Check Point 3 : Outdoor unit fan, heat exchanger check
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 5)
Check Point 5 : Check the refrigerant amount
Leak check
02-35
<Cooling operation>
OK
<Heating operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
EEV open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3".
Check Point 2 : Check the EEV, strainer
EEV open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3".
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
"Protection stop by "compressor temperature" 110
°C
during compressor
operation""generated 2 times within 24 hours
Trouble shooting 33
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Indicate or Display:
Error code : A3
POWER
MODE
ERROR
2
0
1
)
6
L
(
)
2
L
(
)
1
L
(
(L5)
(L4)
(L3)
3
PUMP
DOWN
LOW
NOISE
PEAK
CUT
Outdoor unit : Model 45.54