Trouble shooting 13
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Human sensor error
Indoor unit Main PCB
2. Sensor failure
e
r
u
li
a
f
B
C
P
n
i
a
M
t
i
n
u
r
o
o
d
n
I
.
3
e
r
u
li
a
f
n
o
it
c
e
n
n
o
C
.
1
2 When the signal from the sensor is "L"(=0V) for more than 10 min.
1
Detect the open condition of the sensor.
Check Point 1 : Check the connector connection and cable open
Check Point 2 : Conduction check
Check if connector is loose or removed
Check erroneous connection
Check if sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK (Sensor connections error)
OK(Sensor signal error)
Disconnect the sensor and check the 2-3pin
on sensor connector.
>>With conduction : Main PCB failure
>>Without conduction : Sensor failure
Check Point 2 : Voltage check
Disconnect the sensor and check the Voltage
of 1pin of the CN10 on the Main PCB
>>5V: Sensor failure
>>Other than 5V: Main PCB failure