Detective Actuators:
Indoor Unit Controller PCB
Heat Exchanger (MID) Thermistor
Detective details:
Indoor unit thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
Trouble shooting 12
INDOOR UNIT Error Method:
rouble shooting
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
31.7
39.6
49.7
62.9
80.3
103
134
176
17.1
20.8
25.6
Resistance value (k )
Temperature (°C )
Temperature (°C )
0
40
45
50
5
10
15
20
25
30
35
Resistance value (k )
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
DC
BLACK
BLACK
1
2
CN8
H/E Thermistor
Room Temp. Thermistor
BLACK
BLACK
B
1
2
CN32
Indicate or Display:
Error code : 42
POWER
MODE
ERROR
2
5
)
6
L
(
)
2
L
(
)
1
L
(
(L5)
(L4)
(L3)
15
PUMP
DOWN
LOW
NOISE
PEAK
CUT
02-14
Outdoor unit : Model 45.54