![Fujitsu AUXG18LRLB Technical Manual Download Page 70](http://html.mh-extra.com/html/fujitsu/auxg18lrlb/auxg18lrlb_technical-manual_2343782070.webp)
- 64 -
CASSETTE TYPE
AUXG18-5
4LRL
B
External heater output
Specifications of the signal output performance are as shown as follows:
Example:
When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
The output also turns off in defrost operation.
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-11 / D
Output of indoor unit
CN47
Low
→
High
Heater on
High
→
Low
Heater off
60-00 / 2
External input and output
PCB
Output 3
Off
→
On
Heater on
60-09 / B
60-10 / C
On
→
Off
Heater off
Output signal
Condition
Low
→
High
Heater turns on as shown in diagram of heating temperature
Off
→
On
High
→
Low
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
On
→
Off
• Error occurred
• Forced thermo off
• Fan stop protection
Off
Off
On
Tr-Ts
Tr-Ts=-1°C
Tr-Ts=-10°C
Tr-Ts=-3°C
Tr-Ts=-12°C
Summary of Contents for AUXG18LRLB
Page 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Page 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Page 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Page 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Page 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Page 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Page 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...