- 104 -
CASSETTE
TYPE
AUXG18-54L
RLB
5. Capacity compensation rate for pipe length and height
difference
5-1. Model: AOYG18LBCA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
Height differenc
e
H (m)
Indoor unit is higher than outdoor
unit *1
20
-
-
-
0.952
0.951
10
-
-
0.980
0.968
0.966
7.5
-
0.988
0.984
0.972
0.970
5
0.995
0.992
0.988
0.976
0.974
0
1.003
1.000
0.996
0.983
0.982
Indoor unit is lower than outdoor
unit *2
-5
1.003
1.000
0.996
0.983
0.982
-7.5
-
1.000
0.996
0.983
0.982
-10
-
-
0.996
0.983
0.982
-20
-
-
-
0.983
0.982
HEATING
Pipe length (m)
5
7.5
10
20
30
He
igh
t differ
ence
H (m)
Indoor unit is higher than outdoor
unit *1
20
-
-
-
0.954
0.908
10
-
-
0.998
0.954
0.908
7.5
-
1.000
0.998
0.954
0.908
5
0.989
1.000
0.998
0.954
0.908
0
0.989
1.000
0.998
0.954
0.908
Indoor unit is lower than outdoor
unit *2
-5
0.984
0.995
0.993
0.950
0.903
-7.5
-
0.993
0.991
0.947
0.901
-10
-
-
0.988
0.945
0.899
-20
-
-
-
0.935
0.890
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
Summary of Contents for AUXG18LRLB
Page 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Page 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Page 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Page 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Page 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Page 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Page 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...