![Fujitsu AUXG18LRLB Technical Manual Download Page 62](http://html.mh-extra.com/html/fujitsu/auxg18lrlb/auxg18lrlb_technical-manual_2343782062.webp)
- 56 -
CASSETTE TYPE
AUXG18-5
4LRL
B
10-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3.
"Combination of external input and output"
on page 57.
When indicator, etc. are connected directly
Example:
Function setting 60 is set to "00"
When connecting with a device equipped with a power supply
Example:
Function setting 60 is set to "00"
External input and output PCB
• A twisted pair cable (22AWG) should be used.
• Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A
• For details, refer to Chapter 10-3.
"Combination of external input and output"
on page 57.
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
1
2
Connected device
CN47
PCB
Connected unit
Relay
(Operation status)
-
+
1
2
3
4
5
6
Power supply
Power supply
Power supply
PCB
Connected device 1
(Operation status)
Connected device 2
(Error status)
(Indoor unit fan
operation status)
Connected device 3
Example
Summary of Contents for AUXG18LRLB
Page 86: ... 80 CASSETTE TYPE AUXG18 54LRLB ...
Page 104: ... 98 CASSETTE TYPE AUXG18 54LRLB 3 2 Models AOYG30LBTA and AOYG36LBTA ...
Page 105: ... 99 CASSETTE TYPE AUXG18 54LRLB 3 3 Models AOYG45LBTA and AOYG54LBTA ...
Page 106: ... 100 CASSETTE TYPE AUXG18 54LRLB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Page 107: ... 101 CASSETTE TYPE AUXG18 54LRLB 4 2 Model AOYG30LBTA ...
Page 108: ... 102 CASSETTE TYPE AUXG18 54LRLB 4 3 Model AOYG36LBTA ...
Page 109: ... 103 CASSETTE TYPE AUXG18 54LRLB 4 4 Models AOYG45LBTA and AOYG54LBTA ...